MODEL LCA30S-3 LCA30S-5 LCA30S-12 LCA30S-15 LCA30S-24 LCA30S-36 LCA30S-48
MAX OUTPUT WATTAGE[W] 18 30 30 30 31.2 32.4 33.6
DC OUTPUT 3V 6A 5V 6A 12V 2.5A 15V 2A 24V 1.3A 36V 0.9A 48V 0.7A
SPECIFICATIONS
MODEL LCA30S-3 LCA30S-5 LCA30S-12 LCA30S-15 LCA30S-24 LCA30S-36 LCA30S-48
INPUT
VOLTAGE[V] AC85 - 132 1for DC110 - 170
CURRENT[A]
ACIN 100V
0.7typ (Io=100%)
FREQUENCY[Hz] 47 - 440 or DC
EFFICIENCY[%] 69typ 75typ 80typ 81typ 82typ 80typ 80typ
INRUSH CURRENT[A]
ACIN 100V
25typ (Io=100%)(
At cold start)
LEAKAGE CURRENT[mA]
0.5max (60Hz,According to UL,CSA and DEN-AN)
OUTPUT
VOLTAGE[V] 3 5 12 15 24 36 48
CURRENT[A] 6 6 2.5 2 1.3 0.9 0.7
LINE REGULATION[mV] 20max 20max 48max 60max 96max 144max 192max
LOAD REGULATION[mV] 40max 40max 100max 120max 150max 240max 300max
RIPPLE[mVp-p]
0to+50
C
*1
80max 80max 120max 120max 120max 150max 150max
-10-0
C
*1
140max 140max 160max 160max 160max 200max 200max
RIPPLE NOISE[mVp-p]
0to+50
C
*1
120max 120max 150max 150max 150max 250max 350max
-10-0
C
*1
160max 160max 180max 180max 180max 300max 400max
TEMPERATURE REGULATION[mV]
50max 50max 120max 150max 240max 360max 480max
DRIFT[mV]
*2
20max 20max 48max 60max 96max 144max 192max
START-UP TIME[ms] 100max (ACIN 85V,Io=100%)
HOLD-UP TIME[ms] 10typ (ACIN 85V,Io=100%)20typ (ACIN 100V,Io=100%)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V]
2.85 - 3.6
Fixed ("Y"which can be adjusted the output is available as optional:5V -5 to +10% : 12,15,24,36,48V t10%)
OUTPUT VOLTAGE SETTING[V]
xx 4.9 - 5.3 11.5 - 12.5 14.4 - 15.6 23.0 - 25.0 34.5 - 37.5 46.0 - 50.0
PROTECTION
CIRCUIT AND
OTHERS
OVERCURRENT PROTECTION
Works over 105% of rating and recovers automatically
OVERVOLTAGE PROTECTION
4.00V min Works over 115% of rating,by zener diode clamping
OPERATING INDICATION
Not provided
REMOTE SENSING Not provided
REMOTE ON/OFF Not provided
ISOLATION
INPUT-OUTPUT AC2,000V 1minute,Cutoff current = 10mA,DC500V 50MWmin (At Room Temperature)
INPUT-FG AC2,000V 1minute,Cutoff current = 10mA,DC500V 50MWmin (At Room Temperature)
OUTPUT-FG AC500V 1minute,Cutoff current = 100mA,DC500V 50MWmin (At Room Temperature)
ENVIRONMENT
OPERATING TEMP.,HUMID.AND ALTITUDE
-10 to +60C,20 - 90%RH (Non condensing)(
Refer to DERATING CURVE), 3,000m (10,000feet)max
STORAGE TEMP.,HUMID.AND ALTITUDE
-20 to +75C,20 - 90%RH (Non condensing), 9,000m (30,000feet)max
VIBRATION 10 - 55Hz,19.6m/s2(2G), 3minutes period,60minutes each along X,Y and Z axis
IMPACT 196.1m/s2(20G), 11ms,once each X,Y and Z axis
SAFETY AND
NOISE
REGULATIONS
AGENCY APPROVALS UL60950-1,CSA C22.2 No.234 Complies with DEN-AN
CONDUCTED NOISE Complies with FCC-B,VCCI-B
OTHERS CASE SIZE/WEIGHT 50X25X132.5mm (WXHXD)/ 150g max
COOLING METHOD Convection