Fast-Acting 1332 x 1 12 (10x38mm) Midget Fuses, 600Vac/dc, 110-30A DCM Series 30 A 15 A 20 A 8A 10 A 5A 100 3A Time-Current Characteristic Curves-Total Clearing 3/4 A Dimensions - in (mm) AMP RATING 1.5" 0.031 (38.1mm) 10 0.41" DCM-2 DCM-6 DCM-12 DCM-18 DCM-34 DCM-2-12 DCM-7 DCM-15 DCM-210 DCM-1 DCM-3 DCM-8 DCM-20 DCM-14 DCM-1-14 DCM-4 DCM-9 DCM-25 DCM-310 DCM-1-12 DCM-5 DCM-10 DCM-30 .1 .01 Designed To: Fuses: DCM 110 thru 30 CURRENT IN AMPS Designed to: Carry 110% of rating for 4 hours AC Opens at 135% of rating within 1 hour AC Maximum Interrupting Rating of 100kA at 600Vac DC Maximum Interrupting Rating of 50kA at 600Vdc DC Minimum Interrupting Rating of 200% rated current at 600Vdc, Recommended fuse blocks/fuse holders See Data Sheets listed below * Open fuse blocks - 1104, 2104 * Finger-safe fuse holders - 1109, 1102, 1103, 2053 * Panel-mount fuse holders - 2114, 2113, 2108, 2112, 2109, 2140 * In-line fuse holders - 2127, 2126 Carton Quantity and Weight Ampere Ratings Carton Qty. Lbs. Kg. 10 0.187 0.088 0-30 1,000 DCM-12 100 DCM-110 10 Electrical Ratings (Catalog Symbol and Amps) IR 100kA AC 1 1 Catalog Symbol: DCM Fast-Acting 110-30A UL Listed: STD. 248-14, (FILE #E19180, GUIDE #JDYX) CSA Certified, C22.2 NO. 248. 14 (CLASS #1422-01, FILE #53787) Interrupting Ratings: 100kA at 600Vac 50kA at 600Vdc TIME IN SECONDS 0.004 (10.3mm) Weight * A full range DC midget fuse. * Melamine tube. * Nickel-plated brass endcaps. The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. (c) 2010 Cooper Bussmann St. Louis, MO 63178 www.cooperbussmann.com 0310 BU-SB091066 Page 1 of 1 Data Sheet 2038