61F-G@N
4
Note: 1. The @ in the model name represents G, G1, G2, G3, G4, or I.
2. The length when using completely insulated, 600-V, 3-core (0.75 mm2) cabtire cables.
Usable cable lengths will become shorter as the cable diameter or number of cores
becomes larger due to increased floating capacity. For details, refer to Safety
Precautions for Floatless Level Controllers.
3. The insulation resistance and dielectric strength are the values between power
terminals and Electrode terminals, between power terminals and contact terminals,
and between Electrode terminals and contact terminals. For details, refer to Safety
Precautions for Floatless Level Controllers.
4. Application is possible with 10 kΩ or less, however, this may cause reset failures.
Type
Items
Low-sensitivity Controller 61F-@ND Two-wire Controller 61F-@NR
Controlling materials
and operating
conditions
For control of liquids with low specific
resistance, such as salt water, wastewater,
acid chemicals, or alkaline chemicals
For control of ordinary purified water
or wastewater. Used with a Two-wire
Electrode Holder (incorporating a
resistor of 6.8 kΩ)
Rated voltage 100/200, 110/220 or 120/240 VAC, 50/60 Hz (supported by the same model)
Allowable Voltage
Fluctuation
85% to 110% of rated voltage
Inter-electrode voltage 8 VAC
Inter-electrode current Approx. 1 mA AC max.
Power consumption GN@: 3 VA max., G1N@, G2N@, IN@: 4 VA max., G3N@: 5.5 VA max.,
G4N@: 8.5 VA max.
Inter-electrode
operation resistance
(recommended values)
0 to approx. 1.8 kΩApprox. 0 to 1.1 kΩ
Inter-electrode release
resistance
(recommended values)
Approx. 5 k to ∞ Ω Approx. 15 k to ∞ Ω
Cable length
(See note 2.)
1 km max. 800 m max.
Output 3 A, 200 VAC (Resistive load)
Ambient operating
temperature
−10 to 55°C
Ambient operating
humidity
45% to 85%
Insulation resistance
(See note 3.)
100 MΩ min. (at 500 VDC)
Dielectric strength
(See note 3.)
2,000 VAC, 50/60 Hz for 1 min.
Life expectancy Electrical: 250,000 operations min.
Mechanical: 10,000,000 operations min.
Weight GN models: 315 g; G1N, G2N, IN models: 410 g; G3N models: 625g;
G4N models: 870 g
Internal Circuit
Diagrams
Example: 61F-GND Example: 61F-GNR
S2
Tb
S1
Tc
S0
Ta
E3E2E1
U
U
U
24 V
8 V
200 V
100 V
0 V Transformer
61F-11ND
Relay Unit
S2
Tb
S1
Tc
S0
Ta
E3E1
U
U
U
24V
8V
200V
100V
0V Transformer
61F-11ND
Relay Unit
■Relay Unit
The Relay Unit can be replaced without
removing the wires for maintenance
inspections. It can also be replaced with
other Relay Units.
Compatibility with
General Purpose Model
(61F-11N)
Terminal Arrangement
General-
purpose
Controller
61F-11N ---
Long-
distance
Controllers
61F-11NL (for 2 km)
61F-11NL (for 4 km)
Provided
High-
sensitivity
Controllers
61F-11NH
Low-
sensitivity
Controller
61F-11ND
Two-wire
Controller
61F-11NR Not
provided
10 9 8 7 11
45 61 2 3
Tb1
ESS S
24 V8 V 24 V
Ta1 Tc1 Tc2 Ta2 Tb2
Relay Unit Circuit
Ordering Example
If you order the components listed
above, the corresponding Relay Unit
will be supplied with the Controller.
Example: If a 61F-GN Controller is
ordered, a 61F-11N Relay
Unit will also be included.