F-Series
F-Series
CIRCUIT BREAKER
The F-Series hydraulic-magnetic high amperage circuit breakers are designed to handle high current applications
in extremely hot and/or cold locations. Due to its time-proven hydraulic-magnetic design, the F-Series load
sensing mechanism is insensitive to changes in ambient or enclosure temperature, providing a consistent trip
point over temperatures ranging from -40°C to +85°C. Additionally, the F-Series circuit breakers come with a
choice of overload time delays, making them ideal for critical applications having inductive loads.
Further, the F-Series breakers are available up to 700A and an optional 25 millivolt metering shunt construction
provides a safe method for monitoring current owing through the breaker by simply connecting a meter
with light gauge wire to the appropriate terminals located on the shunt housing at the rear of the breaker.
Applications can be customized by measuring and displaying percentage of current, watts or safe/danger zones.
Product Highlights:
AC ratings to UL 489
DC voltage ratings up to 700A with metering
shunt section
Consistent trip point over temperatures ranging
from -40°C to +85°C
Optional 25 millivolt metering shunt construction
Typical Applications:
Ideal for applications under
extreme temperatures
Higher Amperage
Applications
Battery Disconnect Systems
Solar Power Systems
Military
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
2 |F-Series Circuit Breaker - General Specications
*Manufacturer reserves the right to change product specification without prior notice.
RESISTANCE PER POLE VALUES
from Line to Load Terminals
(Values Based on Series Trip Circuit Breaker)
Mechanical
Physical
Environmental
Electrical
Designed and tested in accordance with requirements of
specication MIL-PRF-55629 & MIL-STD-202 as follows:
Maximum Voltage 125VDC, 277VAC
Current Ratings Standard current coils: 100, 125,
150, 175, 225, 250 amps. 300,
350, 400, 500, 600, 700 amps
available as parallel pole
construction.
Auxiliary Switch Rating SPDT; 10.1 Amps @ 250VAC, 1.0
Amps @ 65VDC, 0.5 Amps @
80VDC 0.1 Amps @ 125VAC (with
gold contacts).
Insulation Resistance Minimum: 100 Megohms at 500
VDC
Dielectric Strength 1960 VAC, 50/60 Hz for one
minute between all electrically
isolated terminals, except 2500
VAC for one minute between
alarm/aux. switch and main
terminals with contacts in open
and closed position. F-Series
circuit breakers comply with the
8mm spacing & 3750VAC 50/60
Hz dielectric requirements from
hazardous voltage to operator
accessible surfaces, between
adjacent poles and from main
circuits to auxilary circuits per
Publications EN 60950 and VDE
0805.
Resistance, Impedance Values from Line to Load Terminal
- based on Series Trip Circuit
Breaker.
Endurance 4000 ON-OFF operations with rated
Current & Voltage & 4000
operations with no load (8000
operations total) @ 5 per minute.
Parallel Pole construction: 1000
operations with rated Current and
Voltage @ 5 per minute.
Trip Free All F-Series Circuit Breakers will trip
on overload, even when the
actuator is forcibly held in the ON
position.
Trip Indication The operating actuator moves
positively to the OFF position when
an overload causes the circuit
breaker to trip.
Number of Poles 1 - 3 Poles Note: Ratings over 250
Amps only available with parallel
pole.
Internal Circuit Cong. Series (with or without auxiliary
switch), Switch Only (with or without
auxiliary switch).
Available Accessories Factory installed: DC Current
Metering Shunt (25 mV @lr)
Weight Varies depending on construction.
Consult factory.
Standard Colors Housing - Black; Actuator- Black or
White with contrasting ON-OFF
legend.
Shock Withstands 100 Gs, 6ms, sawtooth
while carrying rated current per
Method 213, Test Condition “I”.
Instantaneous and ultra-short
curves tested @ 90% of rated
current.
Vibration Withstands 0.060” excursion from
10-55 Hz, and 10 Gs 55-500 Hz,
at rated current per Method 204C,
Test Condition A. Instantaneous
and ultrashort curves tested at 90%
of rated current.
Moisture Resistance Method 106D; ten 24-hour cycles @
+ 25°C to +65°C, 80-98% RH.56
days @ +85°C, 85% RH.
Salt Spray Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96 hrs).
Thermal Shock Method 107D, Condition A (Five
cycles @ -55°C to +25°C to +85°C
to +25°C).
Operating Temperature -40° C to +85° C
CURRENT
(AMPS)
TOLERANCE
(%)
100 - 700 50
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 3
F-Series Circuit Breaker - General Specications
Table A: Lists UL Listed (489)and CSA Certified (C22.2 N0. 5.1-M) configurations and performance
capabilities as a Molded Case Circuit Brekaer
CURRENT
RATING
CIRCUIT MAX FULL LOAD UL / CSA
TUV
2
CONFIGURATION RATING FREQUENCY PHASE AMPS 1 - 3 POLES 1 or 2 POLES
125 DC --- 50 - 250 50,000 25,000
120 / 240
1
50 / 60 1 100 - 250 10,000 ---
277 50 / 60 1 100 - 250 10,000 ---
208Y / 120 50 / 60 3 100 - 250 10,000 ---
NOTES:
1. 120/240V rating available in 2 or 3 poles. In a 3 pole construction the center pole is Neutral.
2. TUV constructions are not available with AC ratings.
SERIES
F SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS
VOLTAGE
INTERRUPTING
CAPACITY (AMPS)
Electrical Tables
Table A: Lists UL Listed (489)and CSA Certied (C22.2 N0. 5.1-M) congurations and performance capabilities as a Molded Case Circuit
Breaker
Table B: Lists UL Listed congurations and performance capabilities as Circuit Breakers for use in Communications Equipment
(Guide DITT, File E189195), under UL489A
Agency Certifications
UL Listed
UL 489
UL 489A
TUV Certied
Circuit Breakers , Molded Case
(Guide DIVQ, File E129899)
Complies with the requirements
of the CSA Standard for Molded
Case Circuit Breakers,
CANCSA- C22.2 No. 5.1 –M
Circuit Breakers for Use in
Communications Equipment
(Guide DITT, File E189195)
IEC 60947-2
Low Voltage Switchgear and Control
Gear under TUV License No.
R72031058
Notes:
1 120/240V rating available in 2 or 3 poles. In a 3 pole construction the center pole is Neutral.
2 TUV constructions are not available with AC ratings and 150-250 amp ratings only.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
4 |F-Series Circuit Breaker - Handle – Ordering Scheme
1
Series
2
Actuator
3
Poles
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
9
Actuator
Color
10
Mounting
11
Max. App.
Rating
12
Agency
Approval
4
Circuit
F A B 1 A2 0 2 B G14 820
1 SERIES
F
2 ACTUATOR
A Handle, one per pole
S Mid-Trip Handle, one per pole
T Mid-Trip Handle, one per pole & Alarm Switch
8 TERMINAL
Back Connected (Front Mounted Only) Max Rating
1 9 3/8-16 Stud 250A
2 14 3/8-16 Screw, Line & Load 700A
5 14 3/8-16 Short Stud 250A
Front Connected (Back Mounted Only) 11 Max Rating
3 Box Wire Connector, Line & Load 700A
4 14 3/8-16 Screw, Line & Load 700A
10 MOUNTING
Front Mounting Inserts
A 10-32
B ISO M5
Back Mounting Inserts
10-32 screw clearance holes
10-32 screw clearance holes
3 POLES
1 One 2 Two 3 Three
6 FREQUENCY & DELAY
03 DC 50/60Hz, Switch Only
10 7 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
22 AC Short
24 AC Medium
26 AC Long
11 MAXIMUM APPLICATION RATING
VOLTAGE CURRENT
B 125 VDC 700A
C 15 120/240 250A
F 277 VAC 250A
7 16 120/208 VAC 250A
12 AGENCY APPROVAL
A No approvals
G UL489 Listed & CUL Certied
J UL489 Listed, CUL Certied & TUV Certied
T UL489A (Telecom) Listed
9 ACTUATOR COLOR & LEGEND 12,13
Actuator Color I-O ON-OFF Dual Marking Color
White A B 1 Black
Black C D 2 White
Notes:
1 For 100 to 250 amps, select Current Code 825. For 300-400 amps, select Current
Code 840. For 450-700 amps, select Current Code 870.
2 Available with Frequency and Delay code 10 or 20 only, and are not rated for continuous
duty. Delay 10 and 20 are only available with voltage coils.
3 3 Codes M, N, P & Q (Parallel Poles) are supplied with factory installed Bus Bar on
Line and Load.
4 4 Metering terminals are female pin type, ref. Molex part number 02-09-1101, model 1189-T.
5 Auxiliary Switch breakers are only available with Series Trip and Switch Only circuits.
On multi-pole breakers, one Auxiliary Switch is supplied, mounted in the extreme right
pole per gure A. Back-Mounted breakers require special mounting provisions when
an Auxiliary Switch is specied.
6 Available with parallel pole construction (circuit codes P and Q, and breakers with
circuit codes M and N).
7 Frequency and delay code 10 is only available with Voltage Coils. Voltage Coils are not
rated for continuous duty.
8 Ratings over 250 amps are only available with Agency Approval code T (UL489A) and
are Parallel Pole conguration (circuit codes M, N, P and Q.) 300-450 amp ratings are
available on two pole breakers. 500-700 amp ratings are available on three pole
breakers.
9 Per UL requirement, an “Anti-Flash Over Barrier” is supplied between poles on multipole
breakers with 3/8 - 16 stud terminals (Terminal Code 1) on AC rated breakers only.
10 Front connected breakers can also be front mounted by utilizing the supplied front panel
mounting inserts. Terminal connections must be made before mounting.
11 Box Wire connector will accept #6 through 250 MCM copper wire.
12 Agency codes G & T must have ON-OFF or dual legends. Agency code J must have
dual legend.
13 Other colors available. Consult factory.
14 Terminals 2,4 & 5 are shipped without terminal hardware.
15 2 or 3 Pole Circuit Breaker Required for 120/240 VAC Rating.
16 3 Pole Circuit Breaker Required for 120/208 VAC Rating.
4 CIRCUIT Parallel Pole Construction:
A 1 Switch Only (no coil) M 3,4 Series Trip (Current) with Metering Shunt
B Series Trip (current) N 3,4 Switch Only with Metering Shunt
C 2 Series Trip (voltage) P 3 Series Trip (Current)
Q 3 Switch Only
5 AUXILIARY SWITCH 5
0 without Auxiliary Switch 7 S.P.S.T. 0.110 Q.C. Terminals
2 S.P.D.T. 0.110 Q.C. Terminals (Gold Contacts)
3 S.P.D.T. 0.139 Solder Lug 8 S.P.S.T. 0.187 Q.C. Terminals
4 S.P.D.T. 0.110 Q.C. Terminals 9 S.P.D.T. 0.187 Q.C. Terminals
(Gold Contacts) A 6 S.P.S.T., 0.093 Round
5 S.P.S.T., 0.093 Q.C. Terminals QC Terminals
(Gold Contacts) B 6 S.P.D.T., 0.093 Round
6 S.P.S.T. 0.110 Q.C. Terminals QC Terminals
7 CURRENT RATING (AMPERES)
CODE AMPERES
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS) 7
CODE AMPERES
810 100.000
912 125.00
815 150.00
917 175.00
820 200.00
922 225.00
825 250.00
830 8 300.00
835 8 350.00
840 8 400.00
845 8 450.00
850 8 500.00
860 8 600.00
870 8 700.00
A06 6 DC, 5 DC
A12 12 DC, 10 DC
A18 18 DC, 15 DC
A24 24 DC, 20 DC
A32 32 DC, 25 DC
A48 48 DC, 40 DC
A65 65 DC, 55 DC
B25 125 DC, 100 DC
J06 6 AC, 5 AC
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 5
F-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
Circuit & Terminal Diagrams: in. [mm]
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
6 |F-Series Circuit Breaker - Handle – Circuit & Terminal Diagrams
Circuit & Terminal Diagrams: in. [mm]
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 7
F-Series Circuit Breaker - Handle – Dimensional Specications
Dimensional Specifications: in. [mm]
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
8 |F-Series Circuit Breaker - Handle – Dimensional Specications
Dimensional Specifications: in. [mm]
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 9
F-Series Circuit Breaker - Handle – Dimensional Specications
F-Series breakers are available up to 700A, and are also available with a 25 millivolt metering shunt construction.
This optional construction provides a safe method for monitoring current owing through the breaker by simply
connecting a meter with light gauge wire to the appropriate terminals located on the shunt housing at the rear of
the breaker. You can customize the application by measuring and displaying percentage of current, watts or safe/
danger zones.
Dimensional Specifications: in. [mm]
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
10 |F-Series Circuit Breaker - Handle – Dimensional Specications
Dimensional Specifications: in. [mm]
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 11
F-Series Circuit Breaker - Time Delay Values
22
16
14
12
11
No Trip
No Trip
No Trip
No Trip
No Trip
.700 - 12.0
110 - 1000
10.0 - 110
.475 - 10.0
.013 - .125
10.0 - 160
50.0 - 700
.350 - 4.00
60.0 - 400
6.00 - 40.0
.275 - 2.80
.010 - .070
6.00 - 60.0
32.0 - 350
.130 - 1.30
22.0 - 150
2.50 - 15.0
.140 - .850
.008 - .032
.220 - 20.0
10.0 - 90.0
.027 - .220
4.00 - 25.0
.500 - 3.00
.030 - .190
.006 - .020
.300 - 3.00
1.50 - 15.0
.008 - .130
1.00 - 5.50
.180 - 1.00
.015 - .125
.005 - .020
.050 - 1.30
.500 - 7.00
.004 - .090
.010 - 1.80
.010 - .280
.010 - .050
.004 - .020
.007 - .500
.020 - 3.00
.004 - .045
.004 - .020
.008 - .390
.008 - .080
.008 - .038
.005 - .060
.006 - 2.00
No Trip
No Trip
24
26
Long - AC 26
Short - AC 22 Ultrashort - DC
Short - DC
Medium - DC
Medium - AC 24
DCAC
TRIP TIME IN SECONDS
F SERIES
50/60 HZ SHORT
CURVE NO. 22
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
Long - DC
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
F SERIES
50/60 HZ MEDIUM
CURVE NO. 24
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
F SERIES
50/60 HZ LONG
CURVE NO. 26
TRIP TIME IN SECONDS
PERCENT OF RATED CURRENT
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
12 |Notes
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com
| 13
Sales Representatives, Distributors & Company Prole
Authorized Sales Representatives and Distributors
About Carling
Founded in 1920, Carling Technologies is a leading manufacturer of electrical and electronic switches
and assemblies, circuit breakers, electronic controls, power distribution units, and multiplexed power
distribution systems. With four ISO registered manufacturing facilities and technical sales oces worldwide,
Carling Technologies Sales, Service and Engineering teams do much more than manufacture electrical
components, they engineer powerful solutions! To learn more about Carling please visit
www.carlingtech.com/company-prole.
To view all of Carling’s environmental, quality, health & safety certications please visit
www.carlingtech.com/environmental-certications
Click on a region of the map below to nd your local representatives and distributors or visit
www.carlingtech.com/ndarep.
EUROPE
MIDDLE
EAST
SOUTH
AMERICA
ASIA-PACIFIC
OCEANIA
AFRICA
MEXICO
USA
CANADA
Worldwide Headquarters
Carling Technologies, Inc.
60 Johnson Avenue, Plainville, CT 06062
Phone: 860.793.9281 Fax: 860.793.9231
Email: sales@carlingtech.com
Northern Region Sales Oce: nrsm@carlingtech.com
Southeast Region Sales Oce: sersm@carlingtech.com
Midwest Region Sales Oce: mrsm@carlingtech.com
West Region Sales Oce: wrsm@carlingtech.com
Latin America Sales Oce: larsm@carlingtech.com
Asia-Pacific Headquarters
Carling Technologies, Asia-Pacic Ltd.,
Suite 1607, 16/F Tower 2, The Gateway,
Harbour City, 25 Canton Road,
Tsimshatsui, Kowloon, Hong Kong
Phone: Int + 852-2737-2277 Fax: Int + 852-2736-9332
Email: sales@carlingtech.com.hk
Shenzhen, China: shenzhen@carlingtech.com
Shanghai, China: shanghai@carlingtech.com
Pune, India: india@carlingtech.com
Kaohsiung, Taiwan: taiwan@carlingtech.com
Yokohama, Japan: japan@carlingtech.com
Europe | Middle East | Africa Headquarters
Carling Technologies LTD
4 Airport Business Park, Exeter Airport,
Clyst Honiton, Exeter, Devon, EX5 2UL, UK
Phone: Int + 44 1392.364422 Fax: Int + 44 1392.364477
Email: ltd.sales@carlingtech.com
Germany: gmbh@carlingtech.com
France: sas@carlingtech.com
www.carlingtech.com REV_03_2017
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Carling Technologies:
FA1-A0-03-825-12A-BA FA1-A2-03-825-32A-AA FA1-A2-03-825-32A-BA FA1-B0-11-815-12A-BG FA1-B0-12-815-
42A-BG FA1-B0-12-820-12B-BG FA1-B0-12-825-11A-BG FA1-B0-12-825-12A-BG FA1-B0-12-825-1BA-BG FA1-B0-
12-825-31A-BG FA1-B0-12-825-31A-BJ FA1-B0-12-917-11A-BG FA1-B0-14-810-12A-BG FA1-B0-14-815-11A-BA
FA1-B0-14-815-12A-BG FA1-B0-14-815-12A-BJ FA1-B0-14-815-12B-BG FA1-B0-14-815-31A-BG FA1-B0-14-815-
32A-BG FA1-B0-14-815-3BA-BG FA1-B0-14-820-11A-BA FA1-B0-14-820-12A-BG FA1-B0-14-820-12A-BJ FA1-B0-
14-820-1DB-BG FA1-B0-14-820-22A-BG FA1-B0-14-820-3BA-BG FA1-B0-14-825-11A-BA FA1-B0-14-825-11A-BJ
FA1-B0-14-825-12A-BJ FA1-B0-14-825-12B-BJ FA1-B0-14-825-1DA-BG FA1-B0-14-825-22A-BG FA1-B0-14-825-
22B-BG FA1-B0-14-825-42A-BG FA1-B0-14-825-42B-BJ FA1-B0-14-825-52A-BG FA1-B0-14-912-12A-BG FA1-B0-
14-912-12B-BG FA1-B0-14-917-12A-BG FA1-B0-14-917-41A-BG FA1-B0-14-922-12A-BG FA1-B0-14-922-42B-BJ
FA1-B0-16-810-32A-BG FA1-B0-16-810-42A-BG FA1-B0-16-815-32A-BG FA1-B0-16-820-12A-BG FA1-B0-16-820-
32A-BG FA1-B0-16-825-11A-BG FA1-B0-16-825-11B-BJ FA1-B0-16-825-12A-BT FA1-B0-16-825-31A-BJ FA1-B0-
16-825-32A-BG FA1-B0-16-825-41B-BJ FA1-B2-12-815-12B-BG FA1-B2-12-815-32A-BG FA1-B2-12-825-12B-BG
FA1-B2-12-825-12B-BJ FA1-B2-12-825-22A-BG FA1-B2-12-917-12A-BG FA1-B2-12-922-12A-BG FA1-B2-14-810-
42A-BG FA1-B2-14-815-12A-BG FA1-B2-14-815-32A-BG FA1-B2-14-820-12A-BG FA1-B2-14-820-22A-BG FA1-B2-
14-820-32A-BG FA1-B2-14-820-42A-BG FA1-B2-14-820-52A-BG FA1-B2-14-825-12B-BG FA1-B2-14-825-12B-BJ
FA1-B2-14-825-22A-BG FA1-B2-14-912-12A-BG FA1-B2-14-922-31B-BG FA1-B3-12-912-12A-BG FA1-B4-12-825-
12A-BG FA1-B4-12-912-12A-BG FA1-B4-14-815-12A-BG FA1-B9-12-815-32A-BG FA1-B9-14-810-22A-BG FA1-B9-
14-825-22A-BG FA1-M0-14-825-42A-BG FA1-PB-16-922-22A-BA FA2-A0-03-825-12A-BA FA2-A0-03-825-42A-BA
FA2-B0-12-810-12A-BG FA2-B0-12-815-32B-BG FA2-B0-12-815-52B-BA FA2-B0-12-815-52B-BG FA2-B0-12-820-
12A-BG FA2-B0-12-825-11A-BG FA2-B0-14-810-11A-BG FA2-B0-14-810-12A-BG FA2-B0-14-810-12B-BG FA2-B0-
14-815-11B-BA FA2-B0-14-815-12A-BG FA2-B0-14-815-12B-BG FA2-B0-14-815-42A-BJ FA2-B0-14-820-11A-BA
FA2-B0-14-820-11A-BJ FA2-B0-14-820-12B-BG