SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
PEAK CURRENT
PEAK POWER Note.6
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.) Note.8
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP. Note.5
DC OK REALY CONTACT RATINGS (max.)
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
650ms, 60ms/230VAC 1300ms, 60ms/115VAC at full load
20ms/230VAC 20ms/115VAC at full load
88 ~ 264VAC 124 ~ 370VDC
47 ~ 63Hz
94%
0.94/230VAC 0.99/115VAC at full load
2.6A/115VAC 1.3A/230VAC
56 ~ 65V
33A/115VAC 55A/230VAC
<1mA / 240VAC
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery
29 ~ 33V
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
Protection type : Shut down o/p voltage with auto-recovery
95 5 (TSW : detect on heatsink of power switch)℃±
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
UL508, TUV EN62368-1 approved
,;(meet EN60204-1)
EAC TP TC 004
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
EAC TP TC 020, SEMI F47 approved
-25 ~ +70 (Refer to "Derating Curve")
60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
20 ~ 95% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
±℃ 0.03%/ (0 ~ 50 )
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
169.3K hrs min. MIL-HDBK-217F (25 )
63*125.2*113.5mm (W*H*D)
1.03Kg; 12pcs/13.4Kg/1.06CUFT
POWER FACTOR (Typ.)
SDR-240-48
48V
5A
0 ~ 5A
240W
7.5A
50mVp-p
48 ~ 55V
±1.0%
±0.5%
±1.0%
SDR-240-24
24V
10A
0 ~ 10A
240W
15A
360W (3sec.)
50mVp-p
24 ~ 28V
±1.0%
±0.5%
±1.0%
Features :
SDR-240 series
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note 4)
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds max., please refer to peak loading curves.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
8. After 30 minutes of burn-in.
9. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
240W Single Output Industrial DIN RAIL with PFC Function
High efficiency 94% and low power dissipation
150% peak load capability
Built-in active PFC function, PF>0.93
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
PQ
SEMIF47
File Name:SDR-240-SPEC 2020-04-13
EMC IMMUNITY
EMC EMISSION
Bauar
Sicherheit
egel gema
t gepruf t
od
be
www.
ID 2000000000
tuv.com
wac g
os
EN62368-1 IEC62368-1
TPTC004
Mechanical Specification
Block Diagram
Case No. 979A Unit:mm
DC OK Relay Contact
DETECTION
PWM & PFC CIRCUIT
O.L.P.U.V.P.
EMI FILTER
RECTIFIERS
POWER
SWITCHING FILTER
&
RECTIFIERS +V
DC OK
-V
I/P
FG
CONTROL
O.V.P.
&
O.C.P.
PFC
CIRCUIT
PFC
CONTROL
Terminal Pin No. Assignment (TB1)
Terminal Pin No. Assignment (TB2)
Pin No.
Pin No.
1
1,2
2
3,4
5,6
3
Assignment
Assignment
FG
AC/L
AC/N
DC OUTPUT +V
DC OUTPUT -V
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
35
63
1
2
3
4
5
6
1
2
3
125.2
113.5
TB1 TB2
DC OK
DC OK
+V ADJ.
Relay Contact
+
Contact Close PSU turns on / DC OK.
PSU turns off / DC Fail.
30V/1A resistive load.
Contact Open
Contact Ratings (max.)
SDR-240 series
240W Single Output Industrial DIN RAIL with PFC Function
File Name:SDR-240-SPEC 2020-04-13
360W
120W
10 sec. 3 sec.
SDR-240 series
240W Single Output Industrial DIN RAIL with PFC Function
INPUT VOLTAGE (V) 60Hz
LOAD (%)
AMBIENT TEMPERATURE ( )
LOAD (%)
-25 0
Continuous
For 3 sec. (typ.)
10 20 30 40 50 60 70
60
75
100
112.5
150
100
40
88 110
50
60
70
80
155135 230 264
90
100
(VERTICAL)
Output derating VS input voltageDerating Curve
Peak Loading
360W
( 1 ) ( 2 )
240W
100 sec. 3 sec.
File Name:SDR-240-SPEC 2020-04-13