SPECIFICATION
3200W Power Supply with Single Output DPU-3200 series
File Name:DPU-3200-SPEC 2019-07-29
DPU-3200-24 DPU-3200-48
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE Note.5
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY (Typ.) Note.6
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
AC CURRENT (Typ.) Note.5
24V 48V
133A 67A
0 ~ 133A 0 ~ 67A
3192W 3216W
300mVp-p
23.5 ~ 30V
480mVp-p
47.5 ~ 58.8V
±1.0% ±1.0%
±0.5%
±0.5%
1500ms, 60ms/230VAC at full load
16ms / 230VAC at 75% load 9ms / 230VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
0.97/230VAC at full load
93.5%
COLD START 55A/230VAC
17A/230VAC
<2mA / 230VAC
±0.5%
±0.5%
VOLTAGE TOLERANCE
Note.4
94.5%
OVER TEMPERATURE
OVERLOAD
OVER VOLTAGE
105 ~ 115% rated output power
Protection type : Constant current limiting, shut down O/P voltage 5 sec. after O/P voltage is down low, re-power on to recover
31.5 ~ 37.5V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
63 ~ 75V
PROTECTION
Adjustment of output voltage is allowable to 50 ~ 125% of nominal output voltage
Please refer to the Function Manual in following pages
FUNCTION
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-30 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing℃
±℃ ℃0.03%/ (0 ~ 50 )
ENVIRONMENT
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
WITHSTAND VOLTAGE
UL62368-1, TUV EN62368-1, EAC TP TC 004 approved
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:1.5KVAC
ISOLATION RESISTANCE
MTBF
DIMENSION
PACKING
OTHERS
168K hrs min. Telcordia SR-332 (Bellcore) ; 44.9K hrs min. MIL-HDBK-217F (25 )℃
325.8*107*41mm (L*W*H)
SAFETY &
EMC
(Note 9)
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
2.76Kg;4pcs/12Kg/0.81CUFT
NOTE 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Under variable load application or parallel operation ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to normal
ripple level once the output load is more than 5%.
4. Tolerance : includes set up tolerance, line regulation and load regulation.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. The efficiency is measured at 75% load.
7. If use PV signal to adjust Vo, under certain operating conditions, ripple noise of Vo might slightly go over rating defined in this specification.
8. When 2 or more PSUs are in parallel connection, long cable(s) used for parallel connection might generate higher noise to communication signal. Thus, we
suggest using proper filtering part(s) to avoid interference on communication .
9. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
a mm* mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.600 900 For guidance on how to
perform these EMC tests, please refer to EMI testing of component power supplies. (as available on http://www.meanwell.com)
10. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
Adjustment of constant current level is allowable to 20 ~ 100% of rated current. Please refer to the Function Manual in following pages
OUTPUT VOLTAGE PROGRAMMABLE(PV)
CONSTANT CURRENT LEVEL PROGRAMMABLE(PC)
EMC IMMUNITY
EMC EMISSION
Parameter
Parameter
ESD
Radiated
EFT / Burst
Surge
Conducted
Magnetic Field
Voltage Dips and Interruptions
Conducted
Radiated
Harmonic Current
Voltage Flicker
EN55024 , EN61204-3, EN61000-6-2
Standard
Standard
EN55032 (CISPR32) / EN55011 (CISPR11)
EN55032 (CISPR32) / EN55011 (CISPR11)
EN61000-3-2
EN61000-3-3
EN61000-4-2
EN61000-4-3
EN61000-4-4
EN61000-6-2
EN61000-4-6
EN61000-4-8
EN61000-4-11
Test Level / Note
Test Level / Note
Level 3, 8KV air ; Level 2, 4KV contact
Level 3
Level 3
2KV/Line-Line 4KV/Line-Earth
Level 3
Level 4
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Class B
Class A
-----
-----
ALARM SIGNAL
AUXILIARY POWER
Isolated TTL signal output for T-Alarm and DC-OK. Please refer to the Function Manual in following pages
5V @ 0.3A, tolerance 10%, ripple 150mVp-p, 12V @ 0.8A, tolerance 10%, ripple 450mVp-p±±
REMOTE SENSE
REMOTE ON OFF CONTROL-
Compensate voltage drop on the load wiring up to 0.5V. Please refer to the Function Manual in following pages
By electrical signal or dry contact Power ON: Function Manualshort Power OFF:open. Please refer to the in following pages
RIPPLE & NOISE (max.)
Note.2,3