2
Presentation
Presentation
A timing relay is a component which is designed to time events in industrial
automation systems by closing or opening contacts before, during or after a set
timing period.
There are two main 'families' of timing relays:
b "DIN rail mounted" relays (RE7, RE8, RE9, RE17, REXL…) designed for
mounting on DIN rails in an enclosure,
b "Panel mounted" relays type RE48A designed for mounting on the front of a panel
to give users easy access to the settings.
These relays have one, two or four outputs. Sometimes the second output can be
either timed or instantaneous.
If the power is switched off during the timing period, the relay reverts to its initial
position.
Application examples:
b opening of automatic doors,
b alarm,
b lighting in toilets,
b car park barriers ...
De nitions
The following de nitions will assist in understanding the operation of these relays:
b Relay output:
This is the most common type of output. When the relay is energized, the moving
armature is attracted by the coil and so actuates the contacts, which change state.
When the relay is de-energized, both the armature and the contacts revert to their
initial position.
This type of output allows complete isolation between the supply and the output.
There are three types of output:
C/O: changeover contact, i.e. when the relay is de-energized, the
circuit between the common point C and N/C is closed and when
the relay is operating (coil energized), it closes the circuit between
the common point C and N/O.
CNC
NO
N/C: a contact that is closed without being actuated is called a
Normally Closed (N/C) contact. NC
N/O: a contact that closes when actuated is called a
Normally Open (N/O) contact. NO
b Solid state output:
These outputs are entirely electronic and involve no moving parts; service life is
therefore increased.
b Breaking capacity:
The current value that a contact is capable of breaking in speci ed conditions.
b Mechanical durability:
The number of mechanical operating cycles of the contact or contacts.
b Minimum switching capacity (or minimum breaking capacity):
corresponds to the minimum required current which can ow through the contacts
of a relay .
b G (Gate) Input:
Gate input allows timing in progress to be interrupted without resetting it.
Zelio Time - timing relays
DIN rail mounted relays
RE17 RE7, RE8, RE9 REXL
Panel mounted relays
RE48A
28400-EN
version: 2.0
3
Presentation (continued)
De nitions (continued)
Functions
T iming functions are identi ed by letters.
Main timing
functions Complementary
functions (1) De nitions
A (2) Power on delay relay
Ac On-delay and off-delay relay with control signal
Ad Pulse delayed relay with control signal
Ah Pulse delayed relay (single cycle) with control signal
Ak Asymmetrical On-delay and Off-delay with external
control
At Power on delay relay (summation) with control signal
Aw Off-delay on energization or on opening of control
contact
B (2) Interval relay with control signal
Bw Double interval relay with control signal
C (2) Off-delay relay with control signal
D (2) Symmetrical asher relay (starting pulse off)
Di (2) Symmetrical asher relay (starting pulse on)
H (2) Interval relay
He Pulse-on de-energization
Ht Interval relay (summation) with control signal
KDelay on de-energization (without auxiliary supply)
L (2) Asymmetrical asher relay (starting pulse off)
Li (2) Asymmetrical asher relay (starting pulse on)
Lt Asymmetrical ashing with partial stop of timing
NRetriggerable interval relay with control signal on
ORetriggerable interval delayed relay with control signal
on
PPulse delayed relay with xed pulse length
Pt Pulse delayed relay (summation and xed pulse
length) with control signal off
Qc Star-delta timing
Qe Star-delta timing
Qg Star-delta timing
Qt Star-delta timing
TBistable relay with control signal on
Tt Retriggerable bistable relay with control signal on
WInterval relay with control signal off
(1) Complementary functions enhance the main timing functions.
Example: Ac: timing after closing and opening of control contact.
(2) The most commonly used timing functions.
Zelio Time - timing relays
28400-EN
version: 2.0
4
Selection
Selection table
Selection criteria
b Functions (On-delay or Off-delay, counter , ashing…)
b Supply voltage (example: a/c 12 V…240 V).
b Timing range for a timing relay (example: 0.05 s…100 h)
b T ype of output (contact or solid state) and required Number of contacts.
b Breaking capacity or Rated current of contacts, expressed in Amperes.
This is the maximum current which may ow through the contacts.
Functions Timing
range Supply
voltage T ype of
output Rated
current Relay
A0.1 s…100 h c 12 V 2 C/O contacts 5 A REXL2TMJD
4 C/O contacts 3 A REXL4TMJD
0.1 s…100 h c 24 V 2 C/O contacts 5 A REXL2TMBD
4 C/O contacts 3 A REXL4TMBD
0.1 s…100 h a 24 V 2 C/O contacts 5 A REXL2TMB7
4 C/O contacts 3 A REXL4TMB7
0.1 s…100 h a 120 V 2 C/O contacts 5 A REXL2TMF7
4 C/O contacts 3 A REXL4TMF7
0.1 s…100 h a 230 V 2 C/O contacts 5 A REXL2TMP7
4 C/O contacts 3 A REXL4TMP7
0.1 s…10 s a/c 24…240 V 1 solid state output 0.7 A RE9T A11MW
0.3 s…30 s 0.7 A RE9T A31MW
3 s…300 s 0.7 A RE9T A21MW
40 s…60 min 0.7 A RE9T A51MW
1 s…100 h 0.7 A RE17LAMW
0.02 s…300 h 2 timed C/O contacts 5 A RE48ATM12MW
0.05 s…300 h a/c 24 V, a 1 10…240 V 1 C/O contact 8 A RE7TL1 1BU
0.1 s…3 s 8 A RE8T A61BUTQ
0.1s…10 s 8 A RE8T A11BUTQ
0.3 s…30 s 8 A RE8T A31BUTQ
3 s…300 s 8 A RE8T A21BUTQ
20…30 min 8 A RE8T A41BUTQ
0.05 s…300 h a/c 24 V, a 1 10…240 V ,
a/c 42…48 V 2 C/O contacts 8 A RE7TP13BU
A, Ac, At, B, Bw , C, D, Di, H, Ht 1 s…100 h a 24…240 V 1 solid state output 0.7 A RE17LMBM
1 s…100 h a/c 12 V 1 C/O contact 8 A RE17RMJU
1 s…100 h a/c 12…240 V 1 C/O contact 8 A RE17RMMW
8 A RE17RMMWS
1 s…100 h c 24 V, a 24…240 V 1 C/O contact 8 A RE17RMMU
A, At 1 s…100 h c 24 V, a 24…240 V 1 C/O contact 8 A RE17RAMU
A, At, Aw 0.05 s…300 h a 1 10…240 V, a/c 24 V ,
a/c 42…48 V 1 C/O contact 8 A RE7TM1 1BU
A, At, B, C, D, Di, H, Ht 1 s…10 h c 24 V , a 24…240 V 1 C/O contact 8 A RE17RMEMU
A, B, C, Di 0.02 s…300 h a/c 24…240 V 2 C/O contacts 5 A RE48AML12MW
A, C, D, Di, H, Qg, Qt, W 0.05 s…300 h a 1 10…240 V, a/c 24 V ,
a/c 42…48 V 2 C/O contacts 8 A RE7MY13BU
0.05 s…300 h a/c 24…240 V 2 C/O contacts 8 A RE7MY13MW
A, C, D, Di, H, W 0.05 s…300 h a 1 10…240 V, a/c 24 V ,
a/c 42…48 V 1 C/O contact 8 A RE7ML1 1BU
A, D, Di, H 0.1 s…10 s and
3 s…300 s a/c 24…240 V
a 24…240 V 1 solid state output 0.7 A RE9MS21MW
A1, A2, H1, H2 0.02 s…300 h a/c 24…240 V 2 C/O contacts 5 A RE48AMH13MW
Ac 0.05 s…300 h a 1 10…240 V, a/c 24 V ,
a/c 42…48 V 1 C/O contact 8 A RE7MA1 1BU
2 C/O contacts 8 A RE7MA13BU
Ad, Ah, N, O, P, Pt, T, Tt, W 1 s…100 h c 24 V, a 24…240 V 1 C/O contact 8 A RE17RMXMU
Ak 0.05 s…300 h a 1 10…240 V, a/c 24 V ,
a/c 42…48 V 1 C/O contact 8 A RE7MV1 1BU
Zelio Time - timing relays
28400-EN
version: 2.0
5
Selection (continued)
Selection table (continued)
Functions Timing
range Supply
voltage T ype of
output Rated
current Relay
B1 s…100 h c 24 V, a 24…240 V 1 C/O contact 8 A RE17RBMU
C 0.1 s…10 s a/c 24 V 1 C/O contact 8 A RE8RA1 1BTQ
0.3 s…30 s 8 A RE8RA31BTQ
3 s…300 s 8 A RE8RA21BTQ
1 s…100 h c 24 V, a 24…240 V 1 C/O contact 8 A RE17RCMU
0.1 s…10 s a 1 10…240 V 1 C/O contact 8 A RE8RA1 1FUTQ
0.3 s…30 s 8 A RE8RA31FUTQ
3 s…300 s 8 A RE8RA21FUTQ
20 s…30 min 8 A RE8RA41FUTQ
0.05 s…300 h a/c 24 V, a 1 10…240 V ,
a/c 42…48 V 1 C/O contact 8 A RE7RA1 1BU
8 A RE7RM11BU
2 C/O contacts 8 A RE7RL13BU
0.1 s…10 s a 24…240 V 1 solid state output 0.7 A RE9RA1 1MW7
0.3 s…30 s 0.7 A RE9RA31MW7
3 s…300 s 0.7 A RE9RA21MW7
40 s…60 min 0.7 A RE9RA51MW7
1 s…100 h 0.7 A RE17LCBM
D0.05 s…300 h a/c 24 V, a 1 10…240 V 1 C/O contact 8 A RE7CL1 1BU
0.1 s…10 s 8 A RE8CL1 1BUTQ
0.05 s…300 h a/c 24 V, a 1 10…240 V ,
a/c 42…48 V 2 C/O contacts 8 A RE7CP13BU
H0.05 s…300 h a/c 24 V, a 1 10…240 V 1 C/O contact 8 A RE7PE1 1BU
0.1 s…10 s 8 A RE8PE1 1BUTQ
0.3 s…30 s 8 A RE8PE31BUTQ
3 s…300 s 8 A RE8PE21BUTQ
0.05 s…300 h a/c 24 V, a 1 10…240 V ,
a/c 42…48 V 2 C/O contacts 8 A RE7PP13BU
1 s…100 h a 24…240 V 1 solid state output 0. 7 A RE17LHBM
H, Ht 1 s…100 h c 24 V, a 24…240 V 1 C/O contact 8 A RE17RHMU
He 0.05 s…0.5 s a/c 24 V, a 1 10…240 V 1 C/O contact 8 A RE8PT01BUTQ
K0.05 s…10 min a/c 24…240 V 1 C/O contact 5 A RE7RB1 1MW
0.05 s…0.5 s a/c 24 V, a 1 10…240 V 1 C/O contact 8 A RE8RB51BUTQ
0.1 s…10 s 8 A RE8RB1 1BUTQ
0.3 s…30 s 8 A RE8RB31BUTQ
0.05 s…10 min a/c 24…240 V 2 C/O contacts 5 A RE7RB13MW
L, Li 1 s…100 h c 24 V , a 24…240 V 1 C/O contact 8 A RE17RLMU
1 s…100 h a 24…240 V 1 solid state output 0.7 A RE17LLBM
1 s…100 h a/c 12 V 1 C/O contact 8 A RE17RLJU
0.02 s…300 h a/c 24…240 V 2 timed C/O contacts 5 A RE48ACV12MW
L, Li, Lt 0.05 s…300 h a 1 10…240 V, a/c 24 V ,
a/c 42…48 V 1 C/O contact 8 A RE7CV1 1BU
Qc 0.1 s…10 s a/c 24 V, a 1 10…240 V 1 C/O contact 8 A RE8YG1 1BUTQ
0.3 s…30 s 8 A RE8YG31BUTQ
3 s…300 s 8 A RE8YG21BUTQ
Qe 0.3 s…30 s a/c 24 V 1 NO + 1 NC 8 A RE8Y A32BTQ
0.3 s…30 s a 1 10…240 V 1 NO + 1 NC 8 A RE8Y A32FUTQ
0.3 s…30 s a 380…415 V 1 NO + 1 NC 8 A RE8Y A32QTQ
Qg 0.05 s…300 h a/c 24 V, a 1 10…240 V ,
a/c 42…48 V 1 NO + 1 NC 8 A RE7YR12BU
Qt 0.05 s…300 h a/c 24 V, a 1 10…240 V ,
a/c 42…48 V 2 C/O contacts 8 A RE7Y A12BUè+
W0.1 s…10 s a/c 24 V 1 C/O contact 8 A RE8PD1 1BTQ
0.3 s…30 s 8 A RE8PD31BTQ
3 s…300 s 8 A RE8PD21BTQ
0.1 s…10 s a 1 10…240 V 1 C/O contact 8 A RE8PD1 1FUTQ
0.3 s…30 s 8 A RE8PD31FUTQ
3 s…300 s 8 A RE8PD21FUTQ
0.05 s…300 h a/c 24 V, a 1 10…240 V ,
a/c 42…48 V 2 C/O contacts 8 A RE7PD13BU
W , Ht 0.05 s…300 h a/c 24 V, a 1 10…240 V ,
a/c 42…48 V 1 C/O contact 8 A RE7PM1 1BU
Zelio Time - timing relays
28400-EN
version: 2.0
6
Functions
Functions
U: Supply
R: Relay or solid state output
R1/R2: 2 timed outputs
R2 inst.: The second output is instantaneous if the right
position is selected
T: Timing period
C: Control contact
G: Gate
Ta: Adjustable On-delay
Tr: Adjustable Off-delay
Function diagram :
Relay de-energized
Relay energized
Output open
Output closed
Function A: Power on delay relay
1 output 2 outputs The timing period T begins on
energization.
After timing, the output(s) R close(s).
The second output can be either timed
or instantaneous.
2 timed outputs (R1/R2) or 1 timed output
(R1) and 1 instantaneous output (R2 inst.).
Function Ac: On-delay and off-delay relay with control signal
1 output 2 outputs After power-up, closing of the control
contact C causes the timing period T to
start (timing can be interrupted by
operating the Gate control contact G).
At the end of this timing period, the relay
closes.
When control contact C re-opens, the
timing T starts.
At the end of this timing period T, the
output reverts to its initial position (timing
can be interrupted by operating the Gate
control contact G).
The second output can be either timed
or instantaneous.
T = t1 + t2 + …
T = t’1 + t’2 + … 2 timed outputs (R1/R2) or 1 timed output
(R1) and 1 instantaneous output (R2 inst.).
Function Ad: Pulse delayed relay with control signal
After power-up, pulsing or maintaining control contact C starts the timing T.
At the end of this timing period T, the output R closes.
The output R will be reset the next time control contact C is pulsed or maintained.
Function Ah: Pulse delayed relay (single cycle) with control signal
After power-up, pulsing or maintaining control contact C starts the timing T.
A single cycle then starts with 2 timing periods T of equal duration (start with output
in rest position).
Output R changes state at the end of the rst timing period T and reverts to its initial
position at the end of the second timing period T.
Control contact C must be reset in order to re-start the single ashing cycle.
U
R
T
U
R
1/R2
T
R2 inst.
U
C
t1
G
R
t'1t2 t'2
U
C
R1/R2
T T
R2 inst.
U
R
C
T T
U
R
C
TT T T
Zelio Time - timing relays
28400-EN
version: 2.0
7
Functions (continued)
Functions (continued)
Function Ak: Asymmetrical On-delay and Off-delay with external control
After power-up and closing of the control contact C, timing starts for a period Ta
(timing can be interrupted by operating the Gate control contact G).
At the end of this timing period Ta, the output R closes.
Opening of control contact C causes a second timing period T r to start (timing can be
interrupted by operating the Gate control contact G).
At the end of this timing period T r , the output R reverts to its initial state.
Ta = t1 + t2 + …
T r = t’1 + t’2 + …
Function At: Power on delay relay (summation) with control signal
After power-up, the rst opening of control contact C starts the timing. Timing can be
interrupted each time control contact C closes. When the cumulative total of time
periods elapsed reaches the pre-set value T, the output relay closes.
T = t1 + t2 + …
Function Aw: Off-delay on energization or on opening of control contact
The timing period T starts on energization.
At the end of the timing period T, the output R closes.
Closing of the control contact C makes the output R open.
Opening of control contact C restarts timing period T.
At the end of the timing period T, the output R closes.
Function B: Interval relay with control signal
After power-up, pulsing or maintaining control contact C starts the timing T.
The output R closes for the duration of the timing period T then reverts to its initial
state.
Function Bw: Double interval relay with control signal
On closing and opening of control contact C, the output R closes for the duration of
the timing period T.
U
C
t1
G
R
t'1t2 t'2
U
R
C
t1 t2
U
R
C
T T
U
R
C
TT
U
R
C
TT
Zelio Time - timing relays
28400-EN
version: 2.0
8
Functions (continued)
Function C:Off-delay relay with control signal
1 output 2 outputs After power-up and closing of the control
contact C, the output R closes.
When control contact C re-opens, timing
T starts.
At the end of the timing period, output(s) R
revert(s) to its/their initial state.
The second output can be either timed or
instantaneous.
2 timed outputs (R1/R2) or 1 timed output (R1)
and 1 instantaneous output (R2 inst.).
Function D: Symmetrical asher relay (starting pulse off)
1 output 2 outputs Repetitive cycle with two timing periods T
of equal duration, with output(s) R
changing state at the end of each timing
period T.
The second output can be either timed or
instantaneous.
2 timed outputs (R1/R2) or 1 timed output (R1)
and 1 instantaneous output (R2 inst.).
Function Di: Symmetrical asher relay (starting pulse on)
1 output 2 outputs Repetitive cycle with two timing periods T
of equal duration, with output(s) R
changing state at the end of each timing
period T.
The second output can be either timed or
instantaneous.
2 timed outputs (R1/R2) or 1 timed output (R1)
and 1 instantaneous output (R2 inst.).
Function H: Interval relay
1 output 2 outputs On energization of the relay , timing period
T starts and the output(s) R close(s).
At the end of the timing period T, output(s)
R revert(s) to its/their initial state.
The second output can be either timed or
instantaneous.
2 timed outputs (R1/R2) or 1 timed output (R1)
and 1 instantaneous output (R2 inst.).
U
C
R
T
U
R
1/R2
C
T
R
2 inst.
TTTTTT
U
R
U
R
1/R2
TTTTTT
R
2 inst.
TT T TT
U
R
U
R
1/R2
TT T TT
R
2 inst.
U
R
T
U
1/R2
T
R
2 inst.
Zelio Time - timing relays
Functions (continued)
28400-EN
version: 2.0
9
Functions (continued)
Function He: Pulse-on de-energization
On de-energization, the output R closes for the duration of a timing period T.
Function Ht: Interval relay (summation) with control signal
On energization, the output R closes for the duration of a timing period T then reverts
to its initial state.
Pulsing or maintaining control contact C will again close the output R.
T iming T is only active when control contact C is released and so the output R will not
revert to its initial state until after a time t1 + t2 + … .
The relay memorises the total, cumulative opening time of control contact C and,
once the set time T is reached, output R reverts to its initial state.
T = t1 + t2 + …
Function K: Delay on de-energization (without auxiliary supply)
1 output 2 outputs On energization, the output(s) R close(s).
On de-energization, timing period T starts
and, at the end of this period, the
output(s) R revert to its/their initial state.
Function L: Asymmetrical asher relay (starting pulse off)
Repetitive cycle consisting of two, independently adjustable timing periods Ta and T r .
Each timing period corresponds to a different state of the output R.
Function Li:Asymmetrical asher relay (starting pulse on)
Repetitive cycle consisting of two, independently adjustable timing periods Ta and Tr .
Each timing period corresponds to a different state of the output R.
Function Lt: Asymmetrical ashing with partial stop of timing
Repetitive cycle comprises of two, independently adjustable timing periods Ta and T r .
Each timing period corresponds to a different state of the output R.
Gate control contact G can be operated to partially stop timing periods Ta and Tr .
T r = t1 + t2 + …
Ta = t’1 + t’2 + …
U
R
> 80 ms 80 ms
T < T
U
R
C
t1 t2T
U
R
T
U
R
1
R
2
T
Tr Ta
U
R
Ta Tr
U
R
R
G
t1 t'2t2 t'1
U
Zelio Time - timing relays
Functions (continued)
28400-EN
version: 2.0
10
Functions (continued) Zelio Time - timing relays
Functions (continued)
Function N: Retriggerable interval relay with control signal on
After power-up and an initial control pulse C, the output R closes.
If the interval between two control pulses C is greater than the set timing period T,
timing elapses normally and the output R opens at the end of the timing period. If the
interval is not greater than the set timing period, the output R remains closed until
this condition is met.
Function O: Retriggerable interval delayed relay with control signal on
An initial timing period T begins on energization. At the end of this timing period, the
output R closes.
As soon as there is a control pulse C, the output R reverts to its initial state and
remains in that state until the interval between two control pulses is less than the
value of the set timing period T. Otherwise, the output R closes at the end of the
timing period T.
Function P: Pulse delayed relay with xed pulse length
The timing period T starts on energization.
At the end of this period, the output R closes for a xed time P.
Function Pt: Pulse delayed relay (summation and xed pulse length) with control signal off
On energization, timing period T starts (it can be interrupted by operating control
contact C).
At the end of this period, the output R closes for a xed time P.
Function Qc: Star-delta timing
T iming for star delta starter with contact for switching to star connection.
Function Qe: Star-delta timing
On energization, the star contact closes instantly and timing starts.
At the end of the timing period, the star contact opens.
After a 80 ms pause, the delta contact closes and remains in this position.
T
U
C
R
T
TT T
U
C
R
t<T
T = t1 + t2 + …
P = 500 ms
T 50 ms
U
R
T80 ms
U
R
1
R
2
U
R
TP
t1 t2
U
C
R
P
P = 500 ms
28400-EN
version: 2.0
11
Functions (continued) Zelio Time - timing relays
Functions (continued)
Function Qg: Star-delta timing
Timing for star delta starter with contact for switching to star connection.
Function Qt: Star-delta timing
Timing for star-delta starter with double On-delay period.
Function T: Bistable relay with control signal on
After power-up, pulsing or maintaining of control contact C switches the output on.
A second pulse on the control contact C switches the output R off.
Function Tt: Retriggerable bistable relay with control signal on
After power-up, pulsing or maintaining control contact C switches output R on and
starts timing.
The output switches off at the end of the timing period T or following a second pulse
on the control contact C.
Function W: Interval relay with control signal off
1 output 2 outputs After power-up and opening of the control
contact, the output(s) close(s) for a timing
period T.
At the end of this timing period the
output(s) revert to its/their initial state.
The second output can be either timed or
instantaneous.
2 timed outputs (R1/R2) or 1 timed output (R1)
and 1 instantaneous output (R2 inst.).
TT
50 ms
U
R
1
R
2
U
R
1
R
2TT
50 ms
U
C
R
U
C
R
T t<T
T
U
C
R
U
C
1/R2
T
R2 inst.
28400-EN
version: 2.0
12
RE48ATM12MW
Function A: Delay on energization
RE48ACV12MW
Function L: Asymmetrical ashing, start with output in rest
position Function Li: Asymmetrical ashing, start with output in
operating position
RE48A ML12MW
Function A: Delay on energization Function B: Timing on impulse, one shot
Function C: Timing after opening of control contact Function Di: Symmetrical ashing, start with output in operating position
T T
Un
R
t3 ta tc
t2 tb
t1
Un
Gate
2 - 6
Nor / Inv
Toff Ton
Toff = t1+t2+t3 Ton = ta+tb+tc
R
Toff Toff
Ton
t3 ta
t2 tb
t1 t1
Un
Gate
2 - 6
Nor / Inv
Ton
Ton = t1+t2+t3 T of f = ta+tb+tc
R
Toff Ton
T T
t2
T = t1 + t2 + t3
t1 t3 T T T Tt
Un
Start
Gate
Reset
R
T T T t1 t3
t2
T = t1 + t2 + t3
T T T
Un
Start
Gate
Reset
R
T T t1 t3
t2
T = t1 + t2 + t3
T T
Un
Start
Gate
Reset
Ouput
TTT TTT
t1t2
T = t1 + t2
t1 t2 TTT TTT TTTTTTTT
Un
Start
Gate
Reset
O
utput
Functions (continued) Zelio Time - timing relays
Electronic relays, relay output, 48 x 48
28400-EN
version: 2.0
13
Functions (continued) Zelio Time - timing relays
Electronic relays, relay output, 48 x 48
RE48AMH13MW
Functions A1, A2: Delay on energization Functions H1, H2: Pulse-on energization
Note: If A1 or H1 is selected, only R2 is timed, R1 is instantaneous
T T
Un
R2
R1
T T
Un
R2
R1
28400-EN
version: 2.0
14
Modular relays with solid state output 0.7 A
Single function
Timing ranges Functions V oltages Reference Weight
V kg/lb
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
Az 24…240 RE17LAMW 0.060/
0.132
Ha 24…240 RE17LHBM 0.060/
0.132
Ca 24…240 RE17LCBM 0.060/
0.132
Dual function
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
L,
Li a 24…240 RE17LLBM 0.060/
0.132
Multifunction
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
A,
At,
B,
C,
H,
Ht,
D,
Di,
Ac,
Bw
a 24…240 RE17LMBM 0.060/
0.132
Modular relays with relay output, 1 C/O contact
Single function
Timing ranges Functions V oltages Reference Weight
V kg/lb
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
Bc 24 / a 24…240 RE17RBMU 0.070/
0.154
Cc 24 / a 24…240 RE17RCMU 0.070/
0.154
Dual function
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
A,
At c 24 / a 24…240 RE17RAMU 0.070/
0.154
H,
Ht c 24 / a 24…240 RE17RHMU 0.070/
0.154
L,
Li c 24 / a 24…240 RE17RLMU 0.070/
0.154
z 12 RE17RLJU 0.070/
0.154
Multifunction
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
A,
At,
B,
C,
H,
Ht,
D,
Di,
Ac,
Bw
z 12 RE17RMJU 0.070/
0.154
c 24 / a 24…240 RE17RMMU 0.070/
0.154
z 12…240 RE17RMMW 0.070/
0.154
RE17RMMWS 0.070/
0.154
Ad,
Ah,
N,
O,
P,
Pt,
T,
Tt,
W
c 24 / a 24…240 RE17RMXMU 0.070/
0.154
1 s,
10 s,
1 min
10 min,
1 h,
10 h
A,
At,
B,
C,
H,
Ht,
D,
Di
c 24 / a 24…240 RE17RMEMU 0.070/
0.154
PF
121100
A
RE17LAMW
PF121103B
RE17LLBM
PF
121113
A
RE17RpMp
Zelio Time - timing relays
Modular relays with solid state or relay output,
width 17.5 mm/0.69 in.
References
Solid state output
v Multifunction, dual function or single function
v Multi-range (7 selectable ranges)
v Multivoltage
v Solid state output: 0.7 A
v Screw terminals
Relay output, 1 C/O contact
v Dual function or single function
v Multi-range (7 selectable ranges)
v Multivoltage
v 1 relay output: 8 A
v Screw terminals
v State indication by 1 LED
v Option of supplying a load in parallel
v 3-wire sensor control option
28400-EN
version: 2.0
15
References
Single function
Timing
ranges Functions Voltages Reference Weight
V kg/lb
0.1 s…10 s Az 24… 240 V RE9TA11MW 0.110/
0.243
Cz 24… 240 V RE9RA11MW7 0.110/
0.243
0.3 s…30 s Az 24… 240 V RE9TA31MW 0.110/
0.243
Cz 24… 240 V RE9RA31MW7 0.110/
0.243
3 s…300 s Az 24… 240 V RE9TA21MW 0.110/
0.243
Cz 24… 240 V RE9RA21MW7 0.110/
0.243
40 s…60 min Az 24… 240 V RE9TA51MW 0.110/
0.243
Cz 24… 240 V RE9RA51MW7 0.110/
0.243
Multifunction
0.1 s…10 s,
0.3 s…30 s Az 24… 240 V RE9MS21MW 0.110/
0.243
H,
D,
Di
a 24…240 V
Zelio Time - timing relays
Industrial single or multifunction relays,
solid state output, width 22.5 mm/0.89 in.
References
RE9pAp1MW
PF121100A
RE9MS21MW
Solid state output
v Multifunction or single function
v Multivoltage
v Screw terminals
v T ransparent, hinged and sealable ap on front panel
PF105869
28400-EN
version: 2.0
16
References
Single function
Timing
ranges Functions No. of relay
outputs Voltages Reference Weight
V kg/lb
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
B1z 24…240 RE88865125
(1) 0.090/
0.198
C1z 24…240 RE88865135
(1) 0.090/
0.198
0.6 s,
2.5 s,
20 s,
160 s
K2z 24…240 RE88865265
(1) 0.090/
0.198
Selectable
interswitching
time
Functions No. of relay
outputs Voltages Reference Weight
kg/lb
20 ms,
40 ms,
60 ms,
80 ms,
100 ms,
120 ms,
140 ms
Q1z 24…240 RE88865175
(1) 0.090/
0.198
a 230 / 380 RE88865176
(1) 0.090/
0.198
Dual function
Timing
ranges Functions No. of relay
outputs Voltages Reference Weight
kg/lb
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
A,
At 2z 24…240 RE88865215
(1) 0.090/
0.198
1z 24…240 RE88865115
(1) 0.090/
0.198
H,
Ht 1z 24…240 RE88865145
(1) 0.090/
0.198
L,
Li 1z 24…240 RE88865155
(1) 0.090/
0.198
Multifunction
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
A,
At,
B,
C,
H,
Ht,
Di,
D,
Ac,
Bw
1z 24…240 RE88865105
(1) 0.090/
0.198
1z 12 RE88865100
(1) 0.090/
0.198
1z 12…240 RE88865103
(1) 0.090/
0.198
RE88865503
(2) 0.090/
0.198
2 of which 1
convertible to
instantaneous
z 24…240 RE88865305
(1) 0.090/
0.198
z 12 RE88865300
(1) 0.090/
0.198
z 12…240 RE88865303
(1) 0.090/
0.198
Ad,
Ah,
N,
O
P,
Pt,
Tl,
Tt,
W
1z 24…240 RE88865185
(1) 0.090/
0.198
2z 24…240 RE88865385
(1) 0.090/
0.198
(1) Connection by screw terminals.
(2) Connection by spring terminals.
PF516208
RE88865125
PF516211
RE88865155
Zelio time - timing relays
Industrial single, dual or multifunction relays,
relay output, width 22.5 mm/0.89 in.
References
Output 1 C/O and 2 C/O contacts
v Multifunction, dual function or single function
v Multiple timing ranges (7 switchable ranges)
v Multivoltage
v 1 and 2 relay outputs: 8 A - 250 V (10 A UL)
v Screw or spring terminals
v State indication by 1 LED
v Option of supplying a load in parallel
v 3-wire sensor control option
28400-EN
version: 2.0
17
References (continued)
Timing
ranges Functions No. of relay
outputs Voltages Reference Weight
V kg/lb
0.05 s…300 h
(10 ranges) A,
Aw,
At
1z 24,
a 1 10…240,
z 42…48
RE7TM11BU 0.150/
0.331
Ac 1z 24,
a 1 10…240,
z 42…48
RE7MA11BU 0.150/
0.331
2z 24,
a 1 10…240,
z 42…48
RE7MA13BU
(symmetrical) 0.150/
0.331
Ak 1z 24,
a 1 10…240,
z 42…48
RE7MV11BU 0.150/
0.331
C1z 24,
a 1 10…240,
z 42…48
RE7RA11BU 0.150/
0.331
1z 24,
a 1 10…240,
z 42…48
RE7RM11BU
(low level contact) 0.150/
0.331
2z 24,
a 1 10…240,
z 42…48
RE7RL13BU
(low level contact) 0.150/
0.331
Ht,
W1z 24,
a 1 10…240,
z 42…48
RE7PM11BU 0.150/
0.331
L,
Li,
Lt
1z 24,
a 1 10…240,
z 42…48
RE7CV11BU 0.150/
0.331
A,
C,
H,
W,
D,
Di
1z 24,
a 1 10…240,
z 42…48
RE7ML11BU 0.150/
0.331
A1z 24,
a 1 10…240 RE7TL11BU 0.150/
0.331
2z 24,
a 1 10…240,
z 42…48
RE7TP13BU 0.150/
0.331
H1z 24,
a 1 10…240 RE7PE11BU 0.150/
0.331
2z 24,
a 1 10…240,
z 42…48
RE7PP13BU 0.150/
0.331
D1z 24,
a 1 10…240 RE7CL11BU 0.150/
0.331
2z 24,
a 1 10…240,
z 42…48
RE7CP13BU 0.150/
0.331
W2z 24,
a 1 10…240,
z 42…48
RE7PD13BU 0.150/
0.331
Qt 2z 24,
a 1 10…240,
z 42…48
RE7YA12BU 0.150/
0.331
Qg 2z 24,
a 1 10…240,
z 42…48
RE7YR12BU 0.150/
0.331
A,
C,
H,
W,
D,
Di,
Qg,
Qt
2z 24,
a 1 10…240,
z 42…48
RE7MY13BU 0.150/
0.331
2z 24…240 RE7MY13MW 0.150/
0.331
0.05 s…10 min
(7 ranges) K1z 24…240 RE7RB11MW 0.150/
0.331
2z 24…240 RE7RB13MW 0.150/
0.331
PF103444SE
RE7TM11BU
PF105863SE
RE7MA11BU
PF516221
RE7CV11BU
Zelio time - timing relays
Industrial single, dual or multifunction relays,
relay output, width 22.5 mm/0.89 in.
References (continued)
Output 1 C/O and 2 C/O contacts
v Multifunction, dual function or single function
v Multiple timing ranges
v Multivoltage
v T ransparent, hinged and sealable ap on front panel
28400-EN
version: 2.0
18
References
Timing
ranges Functions Voltages Unit
reference (1) Weight
V kg/lb
0.05 s…0.5 s Kz 24,
a 1 10…240 RE8RB51BUTQ 0.110/
0.243
He z 24,
a 1 10…240 RE8PT01BUTQ 0.110/
0.243
0.1 s…3 s Az 24,
a 1 10…240 RE8TA61BUTQ 0.110/
0.243
0.1 s…10 s Az 24,
a 1 10…240 RE8TA11BUTQ 0.110/
0.243
Cz 24 RE8RA11BTQ 0.110/
0.243
a 1 10…240 RE8RA11FUTQ 0.110/
0.243
Dz 24,
a 1 10…240 RE8CL11BUTQ 0.110/
0.243
Kz 24,
a 1 10…240 RE8RB11BUTQ 0.110/
0.243
Hz 24,
a 1 10…240 RE8PE11BUTQ 0.110/
0.243
Qc z 24,
a 1 10…240 RE8YG11BUTQ 0.110/
0.243
Wz 24 RE8PD11BTQ 0.110/
0.243
a 1 10…240 RE8PD11FUTQ 0.110/
0.243
0.3 s…30 s Az 24,
a 1 10…240 RE8TA31BUTQ 0.110/
0.243
Cz 24 RE8RA31BTQ 0.110/
0.243
a 1 10…240 RE8RA31FUTQ 0.110/
0.243
Hz 24,
a 1 10…240 RE8PE31BUTQ 0.110/
0.243
Kz 24,
a 1 10…240 RE8RB31BUTQ 0.110/
0.243
Qc z 24,
a 1 10…240 RE8YG31BUTQ 0.110/
0.243
Qe z 24 RE8YA32BTQ 0.110/
0.243
a 1 10…240 RE8YA32FUTQ 0.110/
0.243
a 380…415 RE8YA32QTQ 0.110/
0.243
Wz 24 RE8PD31BTQ 0.110/
0.243
a 1 10…240 RE8PD31FUTQ 0.110/
0.243
3 s…300 s Az 24,
a 1 10…240 RE8TA21BUTQ 0.110/
0.243
Cz 24 RE8RA21BTQ 0.110/
0.243
a 1 10…240 RE8RA21FUTQ 0.110/
0.243
Hz 24,
a 1 10…240 RE8PE21BUTQ 0.110/
0.243
Qc z 24,
a 1 10…240 RE8YG21BUTQ 0.110/
0.243
Wz 24 RE8PD21BTQ 0.110/
0.243
a 1 10…240 RE8PD21FUTQ 0.110/
0.243
20 s…30 min Az 24,
a 1 10…240 RE8TA41BUTQ 0.110/
0.243
Ca 1 10…240 RE8RA41FUTQ 0.110/
0.243
(1) These products are sold in packs of 10
Zelio Time - timing relays
Industrial single function relays, optimum,
relay output, width 22.5 mm/0.89 in.
References
v Single function
v Single timing range
v Output 1 C/O contact
v T ransparent, hinged and sealable ap on front panel
PF105867SE
RE8TApppppp
28400-EN
version: 2.0
19
RE88867305
PF516213
RE88867415
PF516212
References
Single function
Timing
ranges Functions No. of relay
outputs Voltages Reference Weight
V kg/lb
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
C2z 24…240 RE88867435 0.080/
0.176
Dual function
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
A,
At 2 z 24…240 RE88867415 0.080/
0.176
Li,
L2z 24…240 RE88867455 0.080/
0.176
Multifunction
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
A,
At,
B,
C,
H,
Ht,
Di,
D,
Ac,
Bw
2 of which 1
instantaneous z 24…240 RE88867305 0.080/
0.176
z 12 RE88867300 0.080/
0.176
z 12…240 RE88867303 0.080/
0.176
Sockets for 1 1-pin relays
Contact
terminal
arrangement
For use with relays Connection Unit
reference
(1)
Weight
kg/lb
Mixed (2) RE88867ppp Connector RXZE2M114 0.054/
0.119
(1) These products are sold in packs of 10
(2) The inputs are mixed with the relay's supply , with the outputs being located on the opposite side
of the socket.
PF516214
RE88867300
Zelio Time - timing relays
Universal plug-in relays, 11-pin,
relay output, width 35 mm/1.38 in.
References
Output 2 C/O contacts
v Multifunction, dual function or single function
v Multiple timing ranges (7 switchable ranges)
v Multivoltage
v 2 relay output: 8 A - 250 V (10 A UL)
v Plug-in
v State indication by 1 LED
v Option of supplying a load in parallel
v 3-wire sensor control option
28400-EN
version: 2.0
20
References
Single function
Timing
ranges Functions No. of relay
outputs Voltages Reference Weight
V kg/lb
1 s,
10 s ,
1 min,
10 min,
1 h,
10 h,
100 h
A2z 24…240 RE88867215 0.080/
0.176
C1z 24…240 RE88867135 0.080/
0.176
Dual function
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
Li,
L1z 24…240 RE88867155 0.080/
0.176
Multifunction
1 s,
10 s,
1 min,
10 min,
1 h,
10 h,
100 h
A,
At,
B,
C,
H,
Ht,
Di,
D,
Ac,
Bw
1z 24…240 RE88867105 0.080/
0.176
z 12 RE88867100 0.080/
0.176
z 12…240 RE88867103 0.080/
0.176
Sockets for 8-pin relays
Contact
terminal
arrangement
For use with relays Unit
reference
(1)
Weight
kg/lb
Mixed (2) RE888671pp,
RE888672pp RUZC2M 0.054/
0.119
(1) These products are sold in packs of 10
(2) The inputs are mixed with the relay's supply , with the outputs being located on the opposite
side of the socket.
PF516215
RE88867215
PF516216
RE88867155
PF516217
RE88867105
Zelio Time - timing relays
Universal plug-in relays, 8-pin,
relay output, width 35 mm/1.38 in.
References
Output 1 C/O or 2 C/O contacts
v Multifunction, dual function or single function
v Multiple timing ranges (7 switchable ranges)
v Multivoltage
v 1 or 2 relay outputs: 8 A - 250 V (10 A UL)
v Plug-in
v State indication by 1 LED
v Option of supplying a load in parallel
v 3-wire sensor control option
28400-EN
version: 2.0
21
References
Single function
Timing
ranges Functions No. of relay
outputs Voltages Reference Weight
V kg/lb
0.1 s…1 s,
1 s…10 s,
0.1 min…1 min,
1 min…10 min,
0.1 h…1 h,
1 h…10 h,
10 h…100 h
(7 switchable
ranges)
A2c 12 REXL2TMJD 0.050/
0.110
c 24 REXL2TMBD 0.050/
0.110
a 24 (50/60 Hz) REXL2TMB7 0.050/
0.110
a 120 (50/60 Hz) REXL2TMF7 0.050/
0.110
a 230 (50/60 Hz) REXL2TMP7 0.050/
0.110
4c 12 REXL4TMJD 0.050/
0.110
c 24
(1) REXL4TMBD 0.050/
0.110
a 24 (50/60 Hz)
(1) REXL4TMB7 0.050/
0.110
a 120 (50/60 Hz) REXL4TMF7 0.050/
0.110
a 230 (50/60 Hz) REXL4TMP7 0.050/
0.110
Sockets for relays
Contact
terminal
arrangement
For use with relays Connection Unit
reference
(2)
Weight
kg/lb
Mixed (3) REXL2TMpp,
REXL4TMpp Screw clamp RXZE2M114
(5) 0.048/
0.106
REXL2TMpp,
REXL4TMpp Connector RXZE2M114M
(6) 0.056/
0.123
Separate (4) REXL2TMpp Connector RXZES108M 0.070/
0.154
REXL4TMpp Connector RXZE2S114M 0.058/
0.128
(1) For c 48 V supply , additional resistor 560 2 W / c 24 V .
For a 48 V , additional resistor 390 4 W / a 24 V .
(2) These products are sold in lots of 10.
(3) The inputs are mixed with the relay's supply , with the outputs being located on the opposite side
of the socket.
(4) The inputs and outputs are separated from the relay supply.
(5) Thermal current Ith: 10 A.
(6) Thermal current Ith: 12 A.
Zelio Time - timing relays
Miniature plug-in relays, relay output
References
PF516219
REXL4TMpp
PF516218
REXL2TMpp
Output, 2 C/O and 4 C/O contacts
v Miniature and plug-in (21 x 27 mm/0.827 x 1.062 in.)
v Single function: function A = delay on energization
v Rated current a 5 A
v 7 timing ranges (0.1 s to 100 h)
v Multivoltage
v Excellent immunity to interference
v Power on and relay energized indication by 2 LEDs
28400-EN
version: 2.0
22
References
8-pin relay
Timing ranges Function No. of relay
outputs Voltages Reference Weight
V kg/lb
1.2 s,
3 s,
12 s,
30 s,
120 s,
300 s,
12 min,
30 min,
120 min,
300 min,
12 h,
30 h,
120 h,
300 h
A1z 24…240 RE48ATM12MW 0.140/
0.309
A1,
A2,
H1,
H2
2 of which 1
instantaneous z 24…240 RE48AMH13MW 0.140/
0.309
1 1-pin relay
1.2 s,
3 s,
12 s,
30 s,
120 s,
300 s,
12 min,
30 min,
120 min,
300 min,
12 h,
30 h,
120 h,
300 h
L,
Li 2z 24…240 RE48ACV12MW 0.140/
0.309
A,
B,
C,
Di
2z 24…240 RE48AML12MW 0.140/
0.309
Sockets
Description Number
of pins For use
with relays Sold in
lots of Unit
reference Weight
kg/lb
IP 20 sockets with
connection by
connector and mixed
contact terminals (1)
8 RE48ATM12MW,
RE48AMH13MW 10 RUZC2M 0.054/
0.119
11 RE48ACV12MW,
RE48AML12MW 10 RUZC3M 0.054/
0.119
IP20 socket with screw
terminal connections
on rear face
11 RE48ACV12MW,
RE48AML12MW 1RE48ASOC1 1AR
Connectors and protective cover
IP20 solder connectors 8 RE48ATM12MW,
RE48AMH13MW 1RE48ASOC8SOLD
11 RE48ACV12MW,
RE48AML12MW 1RE48ASOC11SOLD
Setting protection
cover RE48ATM12MW,
RE48ACV12MW,
RE48AML12MW,
RE48AMH13MW
1RE48ASETCOV
Protective cover
IP64 RE48ATM12MW,
RE48ACV12MW,
RE48AML12MW,
RE48AMH13MW
1RE48AIPCOV
(1) The inputs are mixed with the relay’s supply terminals, with the outputs being located on the
opposite side of the socket
References Zelio Time - timing relays
Analog, electronic relays,
relay output, 48 x 48
Output 2 C/O contacts
v Time unit selector knob
v Multifunction, single function or dual function
v Multirange
v Multivoltage
v 2 relay outputs, 5 A
v Panel-mounted or plug-in
v LED indication
RE48ATM12MW
PF110452
RE48AMH13MW
PF110451
RUZC3M
DF523398
RE48ASOC11AR
109804
RE8ASOC8SOLD RE48ASOC11SOLD
109803
109805
RE48ASETCOV RE48AIPCOV
109806
109807
28400-EN
version: 2.0
23
References
8-pin relay
Timing
ranges Functions No. of relay
outputs Voltages Reference Weight
V kg/lb
99.99 s,
999.9 s,
9999 s,
99 min 59 s,
99.99 min,
999.9 min,
9999 min,
99 h 59 min,
99.99 h,
999.9 h,
9999 h
A2z 24 RE88857409 0.140/
0.309
a 110 RE88857406 0.140/
0.309
a 220…240 RE88857400 0.140/
0.309
A,
B,
C,
D,
Di,
H
1c 12 and
z 24…48 RE88857003 0.100/
0.220
z 24 and
a 1 10…240 RE88857005 0.100/
0.220
z 24 and
z 48 RE88857604 0.100/
0.220
z 24 V and
a 1 10, (50/60 Hz) RE88857607 0.100/
0.220
z 24 and a 24…240,
(50/60 Hz) RE88857601 0.100/
0.220
1 1-pin relay
99.99 s,
999.9 s,
9999 s,
99 min 59 s,
99.99 min,
999.9 min,
9999 min,
99 h 59 min,
99.99 h,
999.9 h,
9999 h
A,
B,
C,
D,
Di,
H
1c 12 and
z 24…48 RE88857103 0.100/
0.220
z 24 and
a 1 10…240 RE88857105 0.100/
0.220
z 24 and
z 48 RE88857704 0.100/
0.220
z 24 V and
a 1 10 (50/60 Hz) RE88857707 0.100/
0.220
z 24 and a 24…240
(50/60 Hz) RE88857701 0.100/
0.220
A1,
A2,
AM,
AMt
2 of which 1
instantaneous c 12 V and
z 42…48 RE88857302 0.140/
0.309
z 24 and
a 110 RE88857307 0.140/
0.309
z 24 V and
a 220…240 RE88857301 0.140/
0.309
Sockets for relays
Number
of pins For use with relays Unit
reference (1) Weight
kg/lb
8-pin connector RE8885740p, RE8885700p, RE8885760pRUZC2M 0.054/
0.119
11-pin RE8885710p, RE8885730p, RE8885770pRUZC3M 0.054/
0.119
(1) These products are sold in packs of 10
.
Zelio Time - timing relays
Panel-mounted universal, plug-in relays,
relay output
References
Output 1 C/O or 2 C/O contacts
v LCD display
v Multifunction or single function
v Multirange
v Multivoltage
v 1 8A relay or 2 relay outputs: 5 A (RE8885740p),
8 A (RE8885730p)
v Reset function on front panel (RE8885730p)
v Memory in the event of mains power failure
(RE 88 857 30p)
v Locking of access to programming (RE8885710p and
RE8885700p)
v Upcount or downcount mode
v Internal supply by lithium battery (10 years at 20 °C)
RE8885740p
RE8885760p
PF112150SEPF516220
28400-EN
version: 2.0
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Schneider Electric:
RE17RLMU RE17RCMU RE17LMBM RE17RMEMU RE17RMXMU RE17RBMU RE17RAMU RE17LCBM
RE17RHMU RE17RMMW