Product Data Sheet
A Regal Brand
www.marathonsp.com 1
EPBCP45
Power Distribution Block
200 Amps 600 Volts AC/DC
Wire Range
Line: (1) 3/0 - #14 AWG (70 mm2 - 2.5 mm2)
Load: (4) #2 - #14 AWG (25 mm2 - 2.5 mm2)
Electrical Ratings
200 Amps
600V per UL 1953 & CSA 22.2 No. 158, class B & C requirements
1000V AC/DC per IEC 60947-7-1 (CE)
Short circuit current ratings (SCCR): See SCCR section below for specications.
CU9 - 90°C connector terminal rating with copper wire
Touch protection: IP-20 (IEC 60529)
Factory & Field Wiring
Agency Compliance
UL Listed, Investigated to UL 1953, File QPQS.E309401
CSA - certifed to C22.2 No. 158, File No. LR19766 (wire classes B & C only)
CE compliant to IEC 60947-7-1
Material Information
Insulator base:
Thermoplastic
Flammability rating of insulator base UL94V0
Insulator base temperature rating: -40°C to 125°C (UL RTI)
Connector: copper, tin plated
Terminal set screws: steel, nickel plated
Connector mounting screws: steel, zinc plated
RoHS compliant
www.marathonsp.com 2PDS 0420 REV-H 12/19/17
Termination Specications
1 For information on copper stranded wire classes please visit:
http://www.marathonsp.com/exible-stranded-wire.php
Copper solid wire range: 10 - 14 AWG
Wire strip length: 7/8 in. (18mm)
IP-20 protection: 3/0 - 2
Terminal screw drive: 6 mm hex
Load Side Wire Size
(CU Stranded) Torque Wires /
Terminal Wire Class (UL) 1
2 5.7 N·m (50 lbf·in) 1 B, C
4 - 6 5.7 N·m (50 lbf·in) 1 B, C, G, H, I (DLO)
8 5.7 N·m (50 lbf·in) 1 - 2 B, C, G, H, I (DLO)
10 4.5 N·m (40 lbf·in) 1 - 2 B, C, G, H, I (DLO)
12 - 14 4.5 N·m (40 lbf·in) 1 - 4 B, C, G, H, I (DLO)
Copper solid wire range: 10 - 14 AWG
Wire strip length: 11/16 in. (17mm)
IP-20 protection: 2 - 14
Terminal screw drive 4 mm hex
Line Side Wire Size
(CU Stranded) Torque Wires /
Terminal Wire Class (UL) 1
3/0 20.3 N·m
(180 lbf·in) 1B, C
2/0 - 2 20.3 N·m
(180 lbf·in) 1 B, C, G, H, I (DLO)
4 20.3 N·m
(180 lbf·in) 1 B, C, G, H, I (DLO)
420.3 N·m
(180 lbf·in) 1 - 2 B, C
6 - 8 20.3 N·m
(180 lbf·in) 1 - 2 B, C, G, H, I (DLO)
10 - 14 5.6 N·m (50 lbf·in) 1 - 2 B, C, I (DLO)
www.marathonsp.com 3PDS 0420 REV-H 12/19/17
Short Circuit Current Ratings (SCCR)
The suitable conductor ranges are limited to the table values only for achieving the SCCR in excess of the default
rating of 10,000A.
Other conductor combinations within the Terminal Specications noted are suitable for achieving a SCCR of
10,000A (the default rating of terminal blocks).
Enclosure size – Investigated with a minimum 16X12X6 enclosure. Use in smaller enclosures is subject to end use
evaluation.
SCCR With Fuses
* Any wire class evaluated (see terminal specication section)
Wire
Class
Suitable
Conductors
Max Overcurrent Protection Fuse Required
Amp Rating / Class SCCR RMS
Sym. Amps
600V. Max
Line Load J T RK1 RK5 G CC
B, C 3/0 - 8 2 - 8 225 225 200 60 60 30 100,000
B, C 3/0 - 8 8 - 12 100 110 100 30 60 30 100,000
G, H, I 2/0 - 8 4 - 8 225 225 200 60 60 30 100,000
G, H, I 2/0 - 8 8 - 12 100 110 100 30 60 30 100,000
(*) 3/0 - 14 2 - 14 None 10,000
Wire
Class
Suitable
Conductors
Overcurrent Protection Circuit Required
Voltage
AC Max.
Line Load Manufacturer Type Max Amperage
SCCR
RMS
Sym.
AMPS
B, C 2/0 - 8 2 - 10 Allen Bradley
140G-J6
140G-J0
140G-J15
140MG-J8
250 65 kA 480
B, C 3-10 (1) 3 - 10
with (1) 10 Siemens NCGA 80 35 kA 480
B, C 3/0 - 4 2 - 10 Square D
JDL36250 250 18kA
480
JGL36250 250 35kA
JJL36250 250 65kA
JLL36250 250 65kA
SCCR With Circuit Breakers
www.marathonsp.com 4PDS 0420 REV-H 12/19/17
Drawing
Mounting (Panel):
For use with M6 or #10 fastener.
Mounting torque to be determined in end use application not to exceed 30 lbf·in (3.4 N·m)
Marker cards:
white plastic inserts to mark circuits available.
Printing options available, consult customer service for specications.
Allen wrenches (6mm):
4 mm 6 mm
S & K tools 45954 45956
Snap-on tools FAML4E FAML6E
MAC tools XDLS4MM XDLS6MM
McMaster Carr 8367A22 8367A24
Armstrong 38-707 38-711
Installation & Accessories