Product Data Sheet EPBCP45 Power Distribution Block 200 Amps 600 Volts AC/DC Wire Range * * Line: (1) 3/0 - #14 AWG (70 mm2 - 2.5 mm2) Load: (4) #2 - #14 AWG (25 mm2 - 2.5 mm2) Electrical Ratings * * * * * * * 200 Amps 600V per UL 1953 & CSA 22.2 No. 158, class B & C requirements 1000V AC/DC per IEC 60947-7-1 (CE) Short circuit current ratings (SCCR): See SCCR section below for specifications. CU9 - 90C connector terminal rating with copper wire Touch protection: IP-20 (IEC 60529) Factory & Field Wiring Agency Compliance * * * UL Listed, Investigated to UL 1953, File QPQS.E309401 CSA - certifed to C22.2 No. 158, File No. LR19766 (wire classes B & C only) CE compliant to IEC 60947-7-1 Material Information * * * * * Insulator base: * Thermoplastic * Flammability rating of insulator base UL94V0 * Insulator base temperature rating: -40C to 125C (UL RTI) Connector: copper, tin plated Terminal set screws: steel, nickel plated Connector mounting screws: steel, zinc plated RoHS compliant A Regal Brand www.marathonsp.com 1 Termination Specifications Line Side Wire Size (CU Stranded) 3/0 2/0 - 2 4 * * * * 20.3 N*m (180 lbf*in) 20.3 N*m (180 lbf*in) 20.3 N*m (180 lbf*in) Wires / Terminal Wire Class (UL) 1 1 B, C 1 B, C, G, H, I (DLO) 1 B, C, G, H, I (DLO) 4 20.3 N*m (180 lbf*in) 1-2 B, C 6-8 20.3 N*m (180 lbf*in) 1-2 B, C, G, H, I (DLO) 10 - 14 5.6 N*m (50 lbf*in) 1-2 B, C, I (DLO) Wire Size Torque Wires / Terminal Wire Class (UL) 1 2 5.7 N*m (50 lbf*in) 1 B, C 4-6 5.7 N*m (50 lbf*in) 1 B, C, G, H, I (DLO) 8 5.7 N*m (50 lbf*in) 1-2 B, C, G, H, I (DLO) 10 4.5 N*m (40 lbf*in) 1-2 B, C, G, H, I (DLO) 12 - 14 4.5 N*m (40 lbf*in) 1-4 B, C, G, H, I (DLO) Copper solid wire range: 10 - 14 AWG Wire strip length: 7/8 in. (18mm) IP-20 protection: 3/0 - 2 Terminal screw drive: 6 mm hex Load Side * * * * Torque (CU Stranded) Copper solid wire range: 10 - 14 AWG Wire strip length: 11/16 in. (17mm) IP-20 protection: 2 - 14 Terminal screw drive 4 mm hex For information on copper stranded wire classes please visit: http://www.marathonsp.com/flexible-stranded-wire.php 1 www.marathonsp.com 2 PDS 0420 REV-H 12/19/17 Short Circuit Current Ratings (SCCR) * * * The suitable conductor ranges are limited to the table values only for achieving the SCCR in excess of the default rating of 10,000A. Other conductor combinations within the "Terminal Specifications" noted are suitable for achieving a SCCR of 10,000A (the default rating of terminal blocks). Enclosure size - Investigated with a minimum 16X12X6 enclosure. Use in smaller enclosures is subject to end use evaluation. SCCR With Fuses Wire Class B, C B, C G, H, I G, H, I (*) Suitable Conductors Max Overcurrent Protection Fuse Required Amp Rating / Class Line Load J T 3/0 - 8 3/0 - 8 2/0 - 8 2/0 - 8 3/0 - 14 2-8 8 - 12 4-8 8 - 12 2 - 14 225 100 225 100 225 110 225 110 RK1 RK5 G CC 200 60 100 30 200 60 100 30 None 60 60 60 60 30 30 30 30 SCCR RMS Sym. Amps 600V. Max 100,000 100,000 100,000 100,000 10,000 * Any wire class evaluated (see terminal specification section) SCCR With Circuit Breakers Suitable Conductors Wire Class Line Load Overcurrent Protection Circuit Required Voltage AC Max. Manufacturer Type Max Amperage SCCR RMS Sym. AMPS 250 65 kA 480 B, C 2/0 - 8 2 - 10 Allen Bradley 140G-J6 140G-J0 140G-J15 140MG-J8 B, C 3-10 (1) 3 - 10 with (1) 10 Siemens NCGA 80 35 kA 480 Square D JDL36250 JGL36250 JJL36250 JLL36250 250 250 250 250 18kA 35kA 65kA 65kA 480 B, C 3/0 - 4 www.marathonsp.com 2 - 10 3 PDS 0420 REV-H 12/19/17 Installation & Accessories * Mounting (Panel): * For use with M6 or #10 fastener. * Mounting torque to be determined in end use application not to exceed 30 lbf*in (3.4 N*m) * Marker cards: * white plastic inserts to mark circuits available. * Printing options available, consult customer service for specifications. * Allen wrenches (6mm): 4 mm 6 mm * S & K tools 45954 45956 * Snap-on tools FAML4E FAML6E * MAC tools XDLS4MM XDLS6MM * McMaster Carr 8367A22 8367A24 * Armstrong38-70738-711 Drawing www.marathonsp.com 4 PDS 0420 REV-H 12/19/17