Cutler-Hammer Molded Case Circuit Breakers 10-225 Amperes January 2001 Vol. 1, Ref. No. [04871 12-21 F-Frame Product Selection Table 12-33. Types ED, EDH, and EDC Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units Suitable for Reverse Feed Maximum Continuous Ampere Rating @40C 240V AC Maximum, 125V DC (Includes Terminals on Load End Only) 65 kAIC @ 240V AC 1 00 kAIC @ 240V AC Type ED Type EDH Catalog Number 100 125 150 175 200 225 3-Pole 2-Pole ED2100 ED2125 ED2150 ED2175 ED2200 ED2225 Catalog Number Price U.S. $ 357. 357. 357. 357. 357. 357. ED3100 ED3125 ED3150 ED3175 ED3200 ED3225 Type EDC Current Limiting 2-Pole Price U.S. $ 885. 885. 885. 885. 885. 885. Catalog Number 200 kAIC @ 240V AC 3-Pole Price U.S. $ EDH2100 EDH2125 EDH2150 EDH2175 EDH2200 EDH2225 850. 850. 850. 850. 850. 850. Catalog Number 2-Pole Price Catalog Number U.S. S EDH3100 EDH3125 EDH3150 EDH3175 EDH3200 EDH3225 1,280. 1,280. 1,280. 1,280. 1,280. 1,280. 3-Pole Price U.S. S EDC2100 EDC2125 EDC2150 EDC2175 EDC2200 EDC2225 1,200. 1,200. 1,200. 1,200. 1,200. 1,200. Catalog Number Price U.S. S EDC3100 EDC3125 EDC3150 EDC3175 EDC3200 EDC3225 1,655. 1,655. 1,655. 1,655. 1,655. 1,655. Note: Instruction Leaflet/FRED Number 29C101 Table 12-34. Type EHD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units Maximum Continuous 277V AC Maximum, 125V DC 480V AC Maximum, 250V DC 14 kAIC @ 277V AC 14 kAIC @ 480V AC @40C Type EHD (Includes Terminals on Load End Only) 1-Pole 2-Pole Catalog Number 10(c) 15 20 25 30 35 40 45 50 60 70 80 90 100 -- Price U.S.S EHD1010 EHD1015(R) EHD1020(c) EHD1025 EHD1030 EHD1035 EHD1040 EHD1045 EHD1050 EHD1060 EHD1070 EHD1080 EHD1090 EHD1100 Catalog Number 123. 123. 123. 123. 123. 123. 123. 123. 123. 123. 238. 239. 238. 238. EHD2010 EHD2015 EHD2020 EHD2025 EHD2030 EHD2035 EHD2040 EHD2045 EHD2050 EHD2060 EHD2070 EHD2080 EHD2090 EHD2100 3-Pole Price Catalog Number U.S.S 387. 387. 387. 387. 387. 387. 387. 387. 387. 387. 505. 505. 505. 505. EHD3010 EHD3015 EHD3020 EHD3025 EHD3030 EHD3035 EHD3040 EHD3045 EHD3050 EHD3060 EHD3070 EHD3080 EHD3090 EHD3100 Price U.S.S 498. 498. 498. 498. 498. 498. 498. 498. 498. 498. 600. 600. 600. 600. (c) Not UL listed. 5 kAIC interrupting rating. (R) UL listed for SWD applications, see NEC Article 240-83 (d). Note: Instruction Leaflet/FRED Number 29C101 Discount Symbol. CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CB-2 F.T*N 12-2 Product Line Overview January 2001 Vol. 1, Ref. No. [0468] Product Line Description Cutler-Hammer Molded Case Circuit Breakers are designed to provide circuit protection for low voltage distribution systems. They are described by NEMA as, ". . . a device for closing and interrupting a circuit between separable contacts under both normal and abnormal conditions," and furthermore as, ". . . a breaker assembled as an integral unit in a supporting and enclosing housing of insulating material." The NEC describes them as, "A device designed to open and close a circuit by non-automatic means, and to open the circuit automatically on a predetermined overload of current, without injury to itself when properly applied within its rating." 12 So designed, Cutler-Hammer circuit breakers protect conductors against overloads and conductors and connected apparatus, such as motors and motor starters, against short circuits. In low voltage distribution systems, there are many varied applications of molded case circuit breakers. Cutler-Hammer offers the most comprehensive family of molded case circuit breakers in the industry. This family of circuit breakers includes: Thermal Magnetic Trip Breakers Electronic rms Trip Breakers Molded Case Switches Motor Circuit Protectors Current Limiting Breakers Special Application Breakers World Breakers Special Calibration All circuit breaker cases are molded from glass-polyester which does not support the growth of fungus. Any parts which are susceptible to the growth of fungus will require special treatment. 20% Adder 50C Calibration Add suffix V to Catalog Number for complete breaker, listed above, when ordering listed ampere ratings for breakers to be used in 50C ambients. Standards and Certifications Molded case circuit breakers are designed to conform with the following standards: Suffix J01 Fungus Treated $325. + 20% Adder Freeze-Tested Circuit Breakers The circuit breakers may be ordered with freeze testing. This option uses special lubrication and mechanical operation is verified at -40C. Suffix F01 Freeze Tested 20% Adder Marine Applications F-Frame circuit breakers can be supplied to meet the following marine specifications: U.S. Coast Guard CFR 46 ABS -- American Bureau of Shipping IEEE 45 These specifications generally require molded case circuit breakers to be supplied with 50C ambient calibration, special nameplating, and plug-in adapter kits. When plug-in adapter kits are used, no terminals need be supplied. Circuit breakers can also be supplied to meet UL489 Supplement SA (Marine Use) and UL489 Supplement SB (Naval Use). UL489 Supplement SA applies to vessels over 65 feet in length. Requirements include 40C ambient calibration, special labeling, and no use of aluminum conductors or terminals. Suffix H08 "Marine" Special non-UL-listed calibrations are available for certain ambient temperatures other than 40C and for frequencies other than 50/60 Hz or DC. Reduced interrupting ratings will apply for 400 Hz applications. Maximum thermal calibration is limited to 135A at 400 Hz. Suffix H01 400 Hz Moisture-Fungus Treatment 10% Adder UL 489 Supplement SB requires 50C ambient calibration, vibration testings, special nameplating and no use of aluminum conductors or terminals. Suffix H09 "Naval" 10% Adder Underwriters Laboratories, Inc., Standard UL489, Molded Case Circuit Breakers and Circuit Breaker Enclosures National Electrical Manufacturers Association Standards Publication No. AB1-1993, Molded Case Circuit Breakers Australian Standard AS 2184, Molded Case Circuit Breakers British Standards Institution Standard BS 4752: Part 1, Switchgear and Control Gear Part 1: Circuit Breakers Canadian Standards Association Standard C22.2 No. 5, Service Entrance and Branch Circuit Breakers International Electrotechnical Commission Recommendations IEC 157-1, Circuit Breakers Japanese T-Mark Standard Molded Case Circuit Breakers South African Bureau of Standards, Standard SABS 156, Standard Specification for Molded Case Circuit Breakers Swiss Electro-Technical Association Standard SEV 157-1, Safety Regulations for Circuit Breakers Union Technique de l'Electricite Standard NF C 63-120, Low Voltage Switchgear and Control Gear Circuit Breaker Requirements Verband Deutscher Elektrotechniker (Association of German Electrical Engineers) Standard VDE 0660, Low Voltage Switchgear and Control Gear, Circuit Breakers Conformance with these standards satisfies most local and international codes, assuming user acceptability and simplified application. Molded case circuit breakers equal or exceed Federal Specification Classification W-C-375b requirements for the particular class associated with the circuit breaker frame being considered. Note: For further information, see Circuit Breaker, CD-ROM SA.74A.01.T.E. For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E 12 Product Line Overview January 2001 Vol. 1, Ref. No. [0469] Quick Reference Table 12-1. Industrial Circuit Breakers Circuit Cont. Breaker Amp. Type Rating @ 40C No. Volts Poles AC DC Type Federal Spec. of Trip W-C375b UL Listed Interrupting Ratings rms Symmetrical Amperes 120 Page Number DC AC Ratings Volts 120/240 240 277 480 600 125 250 125/250 -- -- -- -- 14,000 -- -- -- -- 14,000 12-9 12-9 14,000 -- 14,000 -- 14,000 -- -- -- -- -- -- -- -- 14,000 -- 14,000 -- -- 12-9 12-9 12-9 12-9 12-9 12-9 -- -- -- -- 11-14 11-14 -- 14,000 12-11 12-11 G-Frame GB GB 15 - 100 1 15 - 100 2, 3 120 240 125 N.I.T. 125/250 11a 10b, 11b, 12b, 14b, 15b 65,000 -- -- -- GHB GHB GHB GHB HGHB GQ 15 - 100 15 - 100 15 - 100 15 - 100 15 - 30 15 - 20 1 2, 3 1 2, 3 1 1 120 240 277 277/480 277 277 N.I.T. 125 125/250 125 125/250 125 -- 11a 10b, 11b, 12b, 14b, 15b 12c, 13a, 13b 65,000 -- -- -- 65,000 65,000 GHBS GBHS 15 - 30 15 - 20 1, 2 1, 2 277/480 347/600 -- -- -- -- GC GC 15 - 100 1 15 - 100 2, 3 120 240 125 N.I.T. 125/250 GD GD 15 - 50 2 15 - 100 3 480 480 GHC GHC GHC GHC HGHC 15 - 100 15 - 100 15 - 100 15 - 100 15 - 30 120 240 277 277/480 277 1 2, 3 1 2, 3 1 -- -- 65,000 -- -- 65,000 -- -- -- -- -- -- 14,000 14,000 25,000 14,000 -- -- -- 14,000 -- -- -- -- -- -- -- -- 65,000 65,000 -- -- -- -- 14,000 -- -- -- -- -- 10,000 -- 11a 10b, 11b, 12b, 14b, 15b 65,000 -- -- -- -- -- 65,000 -- -- -- -- -- 125/250 N.I.T. 250 N.I.T. 13b 13b -- -- -- -- 65,000 -- 65,000 -- 14,000 -- 22,000 -- -- -- -- 10,000 10,000 -- 12-8 12-8 125 N.I.T. 125/250 125 125/250 125 12c, 13a 13b 12c, 13a 13b 65,000 -- -- -- 65,000 -- -- -- -- -- -- 65,000 -- -- -- -- -- -- 14,000 -- 14,000 -- 14,000 -- 14,000 -- -- -- -- -- 12-11 12-11 12-11 12-11 12-11 250 -- -- 35,000 -- -- -- -- N.I.T. -- -- -- -- -- -- -- -- 14,000 14,000 25,000 -- -- -- -- -- 14,000 -- -- -- -- 14,000 -- 14,000 -- New E125 Frame E125B 15 - 125 1 277 2, 3, 4 480 N.I.T. -- 25,000 18,000 -- -- 25,000 -- 18,000 -- 35,000 -- 10,000 -- -- -- 10,000 -- 12-16 E125E 15 - 125 2, 3, 4 600Y/347 250 N.I.T. -- -- 25,000 18,000 10,000 10,000 -- 12-16 E125S 15 - 125 1 347 250 2, 3, 4 600Y/347 N.I.T. N.I.T. -- -- 100,000 -- -- -- 85,000 35,000 -- -- 35,000 -- -- 85,000 -- 35,000 22,000 -- 35,000 -- 12-16 E125H 15 - 125 1 347 250 2, 3, 4 600Y/347 N.I.T. -- -- 200,000 -- -- -- 100,000 65,000 -- -- 42,000 -- -- 100,000 -- 65,000 25,000 -- 42,000 -- 12-17 65,000 -- 100,000 -- 200,000 -- -- -- -- 12-21 12-21 12-21 10,000 -- -- -- 10,000 -- 12-21 12-21 F-Frame ED EDH EDC 100 - 225 2, 3 100 - 225 2, 3 100 - 225 2, 3 240 240 240 125 125 125 N.I.T. 12b 14b 1 -- -- -- -- -- -- EHD EHD 15 - 100 1 15 - 100 2, 3 277 480 125 250 N.I.T. 13a 13b -- -- -- -- -- 14,000 18,000 -- -- -- 14,000 -- FDB FDB 15 - 150 2, 3 15 - 150 4 600 600 250 250 N.I.T. 18a -- -- -- -- 18,000 -- 18,000 -- 14,000 14,000 -- 14,000 14,000 -- 10,000 -- 10,000 -- 12-22 12-22 FD FD FD 15 - 225 1 15 - 225 2, 3 15 - 225 4 277 600 600 125 250 250 N.I.T. 13a 22a -- -- -- -- -- -- -- 25,000 65,000 -- 65,000 -- -- -- 10,000 -- -- 25,000 18,000 -- 10,000 -- 25,000 18,000 -- 10,000 -- 12-22 12-22 12-22 HFD HFD HFD 15 - 225 1 15 - 225 2,3 15 - 225 4 277 600 600 125 250 250 N.I.T. 13a 22a -- -- -- -- -- -- -- 65,000 100,000 -- 100,000 -- -- -- 10,000 -- -- 65,000 25,000 -- 22,000 -- 65,000 25,000 -- 22,000 -- 12-22 12-22 12-22 FDC FDC 15 - 225 2, 3 15 - 225 4 600 600 250 250 N.I.T. 24a -- -- -- -- 200,000 -- 200,000 -- 100,000 35,000 -- 100,000 35,000 -- 22,000 -- 22,000 -- 12-22 12-22 63 - 250 2, 3, 4 600 63 - 250 2, 3, 4 600 63 - 250 2, 3, 4 600 250 250 250 I.T I.T I.T -- -- -- -- -- -- -- -- -- 65,000 -- 85,000 -- 100,000 -- 25,000 18,000 -- 35,000 18,000 -- 65,000 25,000 -- 10,000 -- 22,000 -- 22,000 -- 12-28 12-28 12-28 -- -- -- -- -- -- 10,000 -- 10,000 -- 10,000 -- New J250 Frame J250E J250S J250H N.I.T. is non-interchangeable trip unit and I.T. is interchangeable trip unit. Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250V DC. Not defined in W-C-375b. CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog Cutler-Hammer Molded Case Circuit Breakers 10-225 Amperes January 2001 12-19 Vol. 1, Ref. No. [0485] F-Frame Product Description F-Frame Contents Description Page Product Description 12-19 Technical Data and Specifications 12-19 Dimension/Weights 12-20 Product Selection .. 12-20 * All F-Frame Circuit Breakers are HACR rated. * All circuit breakers 10 through 50 amperes are suitable for HID (high intensity discharge) use. * All F-Frame circuit breakers are suitable for reverse feed use. Typical F-Frame Breaker Technical Data and Specifications Table 12-28. UL489 Interrupting Capacity Ratings Circuit Breaker Type Number of Poles ED EDH EDC EHD Interrupting Capacity (Symmetrical Amperes) (kA) Volts DC & Volts AC (50/60 Hz) 240 277 2,3 2,3 2,3 65 100 200 -- 1 2,3 18 FOB 2,3,4 18 FD 1 2,3,4 HFD 1 2,3,4 100 FDC 2,3,4 200 600 125 250 @(R) -- -- 10 10 -- 14 _ 14 14 480 14 -- 25 10 -- 18 10 10 10 65 -- 10 10 25 65 10 65 25 100 35 22 -- 22 (c) DC ratings apply to substantially non-inductive circuits. (R) 2-pole circuit breaker, or two poles of 3-pole circuit breaker. (R) Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA. Table 12-29. IEC 157-1 (PI) Interrupting Capacity Ratings (P1) Circuit Breaker Type Number of Interrupting Capacity (Symmetrical Amperes) (kA) Poles Volts AC (50/60 Hz) Volts DC A ED EDH EDC 2,3 FOB FD 220, 240 380,415 440 500 125 250 @(R) -- 10 10 10 -- 14 -- 10 65 100 200 -- 2,3,4 18 14 1 2,3,4 25 65 HFD 1 2,3,4 65 100 65 65 25 FDC 2,3,4 200 100 100 35 2,3 2,3 -- 14 10 35 35 18 10 10 22 -- 22 (R) DC ratings apply to substantially non-inductive circuits. (R) 2-pole circuit breaker, or two poles of 3-pole circuit breaker. (c) Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA. CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog F.T.N Cutler-Hammer Molded Case Circuit Breakers 10-225 Amperes 12-20 January 2001 Vol. 1, Ref. No. [0486J F-Frame .. f-i -i Dimensions/Weights Table 12-30. Dimensions in Inches (mm) Number of Poles Width 1 1.375(35) 2 2.75 (70) Depth 6(152) 6(152) Breaker Type 3.375 (86) 3.375 (86) 6(152) 6(152) 4.125(105) 5.5(140) 3 4 Table 12-31. Approximate Shipping Weight, Lbs. (Kg) Height 3.375 (86) 3.375 (86) Number of Poles 1 2 3 4 ED, EDH, EDC -- 3(1.361) 4.5(2.041) -- EHD, FOB, FD, HFD, FDC 2 (.907) 3(1.361) 4.5(2.041) 6(2.721) Product Selection This information is presented only as an aid to understanding Catalog Numbers. It is not to be used to build Catalog Numbers for circuit breakers or trip units. Table 12-32. Circuit Breaker Catalog Numbering System FDC 3 100 L J Circuit Breaker Type EHD Number of Poles 1 2 3 4 FOB FD HFD FDC = 1 Pole = 2 Poles = 3 Poles = 4 Poles Trip Ar Suffix E EH K L S V W Y Z 010 015 020 025 030 035 045 050 060 070 080 = = = = = = = = = 100% Protected (4-Pole only) Neutral Pole 50% Protected (4-Pole only) High Magnetic Molded Case Switch Line and Load Terminals Stainless Steel Terminals 50C Calibration Without Terminals Line Terminals Only Aluminum Terminals (< 100 Amperes) 090 100 110 125 150 175 (FD, HFD, FDC, 2-, 3-, 4-Pole Only) 200 (FD,HFD, FDC, 2-, 3-, 4-Pole Only) 225 (FD,HFD, FDC, 2-, 3-, 4-Pole Only) 200 Circuit Breaker Type ED EDH EDC Number of Poles 2 = 2-Pole 3 = 3-Pole Suffix L = Line and Load Terminals W = Without Terminals Y = Line Terminals Only Z = Aluminum Terminals (100 Amperes) X E:T*M For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E Cutler-Hammer Molded Case Circuit Breakers 10-225 Amperes January 2001 Vol. 1, Ref. No. I0489] 12-23 F-Frame Molded Case Switches Table 12-37. Molded Case Switches Molded Case Switches are used as compact switches in applications requiring high current switching capabilities. Molded case switches are constructed of circuit breaker components and are of the high instantaneous automatic type. Molded case switches are listed in accordance with Underwriters Laboratories, Inc., Standard UL 1087. Line and Load Terminals Line and Load Terminals provide wire connecting capabilities for specific ranges of continuous current ratings and wire types. Except as noted, terminals comply with Underwriters Laboratories, Inc., Standards UL486A and UL486B. Unless otherwise specified, F-Frame circuit breakers are factory equipped with load terminals only. Ordering Information F-Frame circuit breakers and molded case switches have load terminals only as standard equipment. When standard line-end terminals (same as standard load-end terminals) are required, add Suffix L to the circuit breaker Catalog Number. When nonstandard or optional line and/or load terminals are required, order by style number. Specify if factory installation is required. Maximum Continuous Ampere Rating @40C 480V AC Maximum, 250V DC 600V AC Maximum, 250V DC Complete Circuit Breaker with Load Side Terminals Only Complete Circuit Breaker with Load Side Terminals Only Catalog Number Catalog Number Price U.S. S 2-Pole 100 EHD2100K 476. FD2100K FD2150K FD2225K 535.00 1,135.00 1,135.00 EHD3100K 570. FD3100K 665.00 1,240.00 1,190.00 150 225 3-Pole 100 150 225 FD3150K FD3225K 4-Pole 100 150 225 E FD4100K 930.00 1,735.00 1,665.00 -- FD4150K FD4225K Note: Molded Case Switches may open above 1800 amperes. Note: Instruction Leaflet/FRED Number 29C101 Table 12-38. Line and Load Terminals Maximum Breaker Amperes Terminal Body Material Wire Type AWG Wire Range Metric Wire Range mm2 Package of 3 Terminals Catalog Number Price U.S. $ Standard Pressure Type Terminals 20 (END) 100 225 Steel Steel Aluminum Cu/AI Cu/AI Cu/AI 14-10 14-1/0 14-4/0 2.54 2.5- 50 25 - 95 3T20FB (c) 3T100FB 3TA225FD 6.10 89.00 Cu/AI Cu/AI Cu Cu/AI 14-4 14-1/0 4-4/0 6 - 300 kcmil 2.5- 25 2.5- 50 25 - 95 16 -150 3TA50FB (R) 3TA100FD 3T150FB 3TA225FDK i 6.10 6.10 6.10 89.00 6.10 Optional Pressure Terminals 50 100 200 225 Aluminum Aluminum Stainless Steel Aluminum (R) Not for use with ED, EDH, EDC breakers. (R) Includes terminal shield kit. Adds approximately 3 inches (76.2) to breaker height. Available for use on 3-pole breaker only. Discount Symbol. CAT.200.01.T.E Price U.S. $ For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CB-2 E:t>N