Operating Instructions
Edition
Commutation reactors
11/2013
SINAMICS drives
SINAMICS DCM
Answers for industry.
SINAMICS DCM commutating reactors
___________________
___________________
___________________
___________________
___________________
SINAMICS
SINAMICS DCM commutating
reactors
Operating Instructions
11/2013
A5E32621741B
Safety notes
1
Description
2
Mechanical installation
3
Electrical installation
4
Configuring
5
Technical data
6
Dimension drawings
7
Appendix
A
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
Order number: A5E32621741B
11/2013 Technical data subject to change
Copyright © Siemens AG 2013.
All rights reserved
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by
personnel qualified
for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
m
aintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 5
Table of contents
1 Safety notes ............................................................................................................................................ 7
1.1 Warning notices ............................................................................................................................. 7
1.2 Safety and application instructions ................................................................................................ 8
2 Description ............................................................................................................................................ 11
3 Mechanical installation .......................................................................................................................... 13
4 Electrical installation.............................................................................................................................. 17
5 Configuring ........................................................................................................................................... 23
5.1 Commutating reactor rectifier assignment ................................................................................... 23
6 Technical data ...................................................................................................................................... 25
7 Dimension drawings .............................................................................................................................. 33
A Appendix............................................................................................................................................... 67
A.1 Customer Service......................................................................................................................... 67
A.2 Environment ................................................................................................................................. 68
A.3 Standards, certifications ............................................................................................................... 69
Table of contents
SINAMICS DCM commutating reactors
6 Operating Instructions, 11/2013, A5E32621741B
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 7
Safety notes
1
1.1
Warning notices
WARNING
Dangerous electrical voltage
Hazardous voltages are present when electrical equipment is in operation.
Severe personal injury or substantial material damage may result if these warnings are not
observed.
Only qualified personnel are permitted to work on or around the equipment.
These personnel must be thoroughly familiar with all the warnings and maintenance
procedures described in these operating instructions.
The successful and safe operation of this device is dependent on correct transport, proper
storage and installation, as well as careful operation and maintenance.
National safety guidelines must be observed.
DANGER
Five safety rules
When carrying out any kind of work on electrical devices, the "five safety rules" according to
EN 50110-1 must always be observed:
1. Disconnect the system.
2. Protect against reconnection.
3. Make sure that the equipment is de-energized.
4. Ground and short-circuit.
5. Cover or enclose adjacent components that are still live.
Note
Use of copper cables for a UL-approved system
For a UL
-approved system use 60/75°C copper conductors only.
Safety notes
1.2 Safety and application instructions
SINAMICS DCM commutating reactors
8 Operating Instructions, 11/2013, A5E32621741B
1.2
Safety and application instructions
DANGER
Dangerous electrical voltage
This equipment is used in industrial high-voltage installations. During operation, this
equipment contains live, bare parts. For this reason, they could cause severe injury or
significant material damage if the required covers are removed, if they are used or operated
incorrectly, or have not been properly maintained.
When the machines are used in non-industrial areas, the installation location must be
protected against unauthorized access (protective fencing, appropriate signs).
CAUTION
Hot surfaces
The surface of the commutating reactors can reach high temperatures.
NOTICE
Component cooling
Provisions for component cooling must be made at the installation site. Power loss data is
given in the technical specifications.
Note
The core of the commutating reactors should not be considered as being a metal part that
can be touched.
Preconditions
The persons responsible for the safety of the plant must ensure that the following conditions
are met:
Basic planning work for the system and all work relating to transportation, assembly,
installation, commissioning, maintenance and repairs is carried out by qualified personnel
and checked by responsible, suitably skilled personnel.
The Operating Instructions and machine documentation are always available.
The technical specifications regarding the applicable installation, connection,
environmental, and operating conditions are always observed.
The plant-specific assembly and safety guidelines are observed and personal protection
equipment is used.
Unqualified personnel are forbidden from using these machines and working near them.
Safety notes
1.2 Safety and application instructions
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 9
These Operating Instructions are intended for qualified personnel and only contain
information and notes relating to the intended purpose of the machines.
Note
Support by Siemens service centers
We recommend engaging the support and services of your local Siemens service center for
all planning, installat
ion, commissioning and maintenance work.
Safety notes
1.2 Safety and application instructions
SINAMICS DCM commutating reactors
10 Operating Instructions, 11/2013, A5E32621741B
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 11
Description
2
Field of application
Disturbances in the feeding supply system occur during the operation of rectifier-feed drives.
Such disturbances are caused by commutation voltage dips that produce a distortion of the
supply system voltage. Commutating reactors are deployed to limit the voltage dips required
for public supply systems. Commutating reactors also limit the current and dampen the
oscillations caused rectifiers.
The commutating reactors in this document are specially adapted to the SINAMICS DCM
rectifier series and ensure optimum conditions for operation of this rectifier.
Structure
The commutating reactors have an open construction (IP00 degree of protection) and
designed for installation in a switch cabinet.
The reactors provide a foot bracket and, depending on the power, connected using screw
terminals or copper busbars.
Available types
3-phase commutating reactors
The spectrum of available 3-phase commutating reactors is oriented on the requirements of
the offered SINAMICS DC MASTER rectifier units.
The rated current of the 3-phase commutating reactors ranges from AC 13 A to AC 2490 A;
the rated voltages range from 400 V to 950 V.
As standard, the commutating reactors are defined with uk = 4% and designed for a line
frequency of 50 to 60 Hz.
1-phase commutating reactors
The 1-phase commutating reactors are designed as 4% commutating reactors in accordance
with the field power sections of the SINAMICS DCM from AC 3 A to AC 85 A. The rated
voltage is 400 V at 50 Hz or 480 V at 60 Hz.
Thre 1-phase commutating reactors can also be used as line reactors in the supply system
feed cable.
Note
2% commutating reactors
2
% commutating reactors are also available on request.
Description
SINAMICS DCM commutating reactors
12 Operating Instructions, 11/2013, A5E32621741B
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 13
Mechanical installation
3
CAUTION
Use protective equipment
Failure to lift the unit properly can lead to physical injury or material damage.
The reactor should be lifted only with suitable equipment (work gloves should be used) and
by appropriately qualified personnel.
CAUTION
Comply with all safety regulations
The user assumes responsibility for installing the reactor in accordance with safety
regulations (e.g. EN, DIN, VDE) and all other relevant national or local regulations affecting
conductor and grounding dimensioning, overcurrent protection, etc.
The reactor must be installed in accordance with safety regulations (e.g. EN, DIN, VDE) as
well as all other applicable national or local regulations. Grounding, conductor
dimensioning, and the appropriate short-circuit protection measures must be carried out
correctly in order to ensure operational safety.
Mechanical installation
SINAMICS DCM commutating reactors
14 Operating Instructions, 11/2013, A5E32621741B
Lifting
NOTICE
Observe when lifting the reactor
In order to prevent the reactor from becoming deformed, no horizontal forces may be
exerted on the lifting eyes.
Do not lift the reactor at the connecting lugs.
Figure 3-1 Lifting the reactor
Mechanical installation
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 15
Mounting position
Alignment
The commutating reactor must be installed in the appropriate orientation in the cooling-air
flow, see following figure.
Cooling air flow
Figure 3-2 Mounting position
Distance from neighboring components
When the reactor is installed in the switch cabinet, a clearance of approximately 100 mm to
neighboring components is recommended. This clearance guarantees the heat dissipation of
the reactors. If the reactor is installed in a cabinet, it must be ventilated adequately.
Mounting holes, fastening screws
The commutating reactor is provided with 4 elongated holes. Layout and dimensions, see
dimension drawing (Section Dimension drawings (Page 33))
The commutating reactor must be fastened with 4 screws.
Table 3- 1 Retaining screws
Commutating reactor
Order number = 6RX1800-...
Screws (4x)
4DK00; 4FK00; 4DE00; 4DE01; 4DE02; 4DE03
M4
4DE04; 4DE05; 4DE06
M5
4DK01; 4FK01; 4DK02; 4FK02; 4GK00; 4DK03; 4FK03; 4DE07
M6
4DK04; 4FK04; 4GK01;
M8
4DK05; 4FK05; 4DK06; 4GK02; 4FK06; 4DK07; 4DK08; 4FK07; 4FK08;
4GK03; 4DK10; 4FK10; 4GK04; 4FK13; 4DK12; 4KK02; 4GK10; 4KK03;
4GK11; 4FK14; 4LK00; 4DK11; 4GK05; 4GK06; 4FK11; 4FK12; 4KK00;
4KK01; 4GK07; 4GK08; 4DK13; 4DK14; 4GK12; 4FK15; 4KK04; 4GK13;
4FK16; 4FK17; 4LK01; 4KK05; 4GK14; 4KK06; 4GK15; 4FK18; 4DK15;
4LK02; 4GK16; 4GK17; 4LK03; 4MK00; 4KK07
M10
Mechanical installation
SINAMICS DCM commutating reactors
16 Operating Instructions, 11/2013, A5E32621741B
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 17
Electrical installation
4
Important safety precautions
WARNING
Dangerous electrical voltage
The devices are operated with high voltages.
All connection work must be performed with power off.
All work on the device must be performed by trained personnel only.
Non-observance of these warnings can result in death, serious personal injury, or
substantial property damage.
Work on an open device must be carried out with extreme caution because external supply
voltages may be present. The power and control terminals may be live even when the
motor is not running.
Even after safety disconnection, the TSE capacitors still carry a dangerous voltage.
Consequently, the unit may be opened only after an appropriate wait time.
The operator is responsible for ensuring that the commutating reactor and other
components are installed and connected in accordance with the recognized technical rules
in the country of installation and applicable regional guidelines. Special attention should be
paid to cable dimensioning, fuses, grounding, shutdown, disconnection, and overcurrent
protection.
Connection
Note
EMC-compliant installation
When the commutating reactors are connected, observe the installation notes for the EMC
-
conform assembly of drives
in the SINAMICS DCM DC Converter Operating Instructions.
Note
Strain relief
Connection cables or busbars must be fixed near the commutating reactor so that no forces
act on the terminals and connection lugs.
Electrical installation
SINAMICS DCM commutating reactors
18 Operating Instructions, 11/2013, A5E32621741B
Connection overview
Figure 4-1 1-phase connection overview
Figure 4-2 3-phase connection overview
Note
Installation sequence
When commutating reactors with SCCR of 20
ms and 100 ms are deployed, semiconductor
fuses must be installed in the rectifier system upstream of the reactor. These interrupt
ing
times are then achieved by the semiconductor fuses that are normally used.
Electrical installation
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 19
Winding connections
Depending on the rated current, the connections are provided as terminal block or as
connection lugs.
Table 4- 1 Connection with terminal block
Commutating reactor
Order number = 6RX1800-...
Stripped length
Tightening torque
4DE00; 4DE01; 4DE02
10 - 11 mm
0.8 Nm
4DE03; 4DE04
13 - 14 mm
2.5 Nm
4DK00; 4FK00
10 mm
1 Nm
4DK01; 4FK01
12 mm
2.4 Nm
4DK02; 4FK02; 4GK00
16 mm
4 Nm
4DK03; 4FK03
18 mm
5 Nm
Table 4- 2 Connection with connection lugs
Commutating reactor
Order number = 6RX1800-...
Screw, nut
Connection lug
thickness (b)
Tightening torque
4DE06; 4DE05
M6
5 mm
6.8 Nm
4DK04; 4FK04; 4GK01; 4DK05; 4FK05; 4DK06; 4GK02;
4FK06; 4DE07
M8 5 mm 17 Nm
4DK07; 4DK08; 4FK07; 4FK08; 4GK03
M12
5 mm
35 Nm
4DK10; 4FK10; 4GK04; 4DK11; 4GK05; 4GK06; 4FK11;
4FK12; 4KK00; 4KK01; 4GK07; 4GK08; 4FK13; 4DK12;
4KK02; 4GK10; 4KK03; 4GK11; 4FK14; 4LK00; 4GK12;
4KK04; 4LK01
M12 10 mm 35 Nm
4DK13; 4DK14; 4FK15; 4GK13; 4FK16; 4FK17; 4KK05;
4GK14; 4KK06; 4GK15; 4FK18; 4DK15; 4LK02; 4GK16;
4GK17; 4LK03; 4MK00; 4KK07
M12 20 mm 35 Nm
1
Screw
4
Cable lug or busbar
2
Spring lock washer / conical spring washer
5
Nut
3
Disk
7
Flat connection (connection lug)
Figure 4-3 Connecting lug
Electrical installation
SINAMICS DCM commutating reactors
20 Operating Instructions, 11/2013, A5E32621741B
3-phase commutating reactors protective conductor connection
Table 4- 3 Protective conductor connection (1)
Commutating reactor
Order number = 6RX1800-...
Screw, nut
Connection lug
thickness (b)
Tightening torque
4DK04; 4FK04; 4GK01; 4DK05; 4FK05; 4DK06; 4GK02;
4FK06
M8 2 mm 17 Nm
4DK07; 4DK08; 4FK07; 4FK08; 4GK03
M12
2 mm
35 Nm
1
Screw
4
Cable lug or busbar
2
Spring lock washer / conical spring washer
5
Nut
3
Disk
6
PE terminal
Figure 4-4 Protective conductor connection (1)
Table 4- 4 Protective conductor connection (2)
Commutating reactor
Order number = 6RX1800-...
Screw, protective
conductor
connection
Thread length
protective
conductor
connection (L)
Tightening torque
4DK10; 4FK10; 4GK04; 4DK11; 4GK05; 4GK06; 4FK11;
4FK12; 4KK00; 4KK01; 4GK07; 4GK08; 4FK13; 4DK12;
4KK02; 4GK10; 4KK03; 4GK11; 4FK14; 4LK00; 4GK12;
4KK04; 4LK01; 4DK13; 4DK14; 4FK15; 4GK13; 4FK16;
4FK17; 4KK05; 4GK14; 4KK06; 4GK15; 4FK18; 4DK15;
4LK02; 4GK16; 4GK17; 4LK03; 4MK00; 4KK07
M12 18 mm 35 Nm
Electrical installation
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 21
1
Screw
4
Cable lug or busbar
2
Spring lock washer / conical spring washer
6
PE terminal
3
Disk
Figure 4-5 Protective conductor connection (2)
1-phase commutating reactors protective conductor connection
For 1-phase commutating reactors, the protective conductor connection is provided as
screwed connection for pin or ring cable lug. See also Chapter Dimension drawings
(Page 33).
Electrical installation
SINAMICS DCM commutating reactors
22 Operating Instructions, 11/2013, A5E32621741B
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 23
Configuring
5
5.1
Commutating reactor rectifier assignment
Assignment of 3-phase commutating reactors
Table 5- 1 Assignment of 3-phase commutating reactors
SINAMICS DCM
I AC
4% reactor 50 Hz
4% reactor 60 Hz
3-ph. 400 V AC
6RA8013-6D...
12.45 A
6RX1800-4DK00
-
6RA8018-6D...
24.9 A
6RX1800-4DK01
-
6RA8025-6D...
49.8 A
6RX1800-4DK02
-
6RA8028-6D...
74.7 A
6RX1800-4DK03
-
6RA8031-6D...
103.75 A
6RX1800-4DK04
-
6RA8075-6D...
174.3 A
6RX1800-4DK05
-
6RA8078-6D...
232.4 A
6RX1800-4DK06
-
6RA8081-6D...
332 A
6RX1800-4DK07
-
6RA8085-6D...
498 A
6RX1800-4DK10
-
6RA8087-6D...
705.5 A
6RX1800-4DK11
-
6RA8091-6D...
996 A
6RX1800-4DK12
-
6RA8093-4D...
1328 A
6RX1800-4DK13
-
6RA8095-4D...
1660 A
6RX1800-4DK14
-
6RA8098-4D...
2490 A
6RX1800-4DK15
-
3-ph. 480 V AC
6RA8013-6F...
12.45 A
6RX1800-4FK00
6RX1800-4DK00
6RA8018-6F... 24.9 A 6RX1800-4FK01 6RX1800-4DK01
6RA8025-6F...
49.8 A
6RX1800-4FK02
6RX1800-4DK02
6RA8028-6F... 74.7 A 6RX1800-4FK03 6RX1800-4DK03
6RA8031-6F...
103.75 A
6RX1800-4FK04
6RX1800-4DK04
6RA8075-6F...
174.3 A
6RX1800-4FK05
6RX1800-4DK05
6RA8078-6F...
232.4 A
6RX1800-4FK06
6RX1800-4DK06
6RA8082-6F..
373.5 A
6RX1800-4FK08
6RX1800-4DK08
6RA8085-6F..
498 A
6RX1800-4FK10
6RX1800-4DK10
6RA8087-6F...
705.5 A
6RX1800-4FK12
6RX1800-4DK11
6RA8091-6F..
996 A
6RX1800-4FK14
6RX1800-4DK12
3-ph. 575 V AC
6RA8025-6G...
49.8 A
6RX1800-4GK00
6RX1800-4FK02
6RA8031-6G...
103.75 A
6RX1800-4GK01
6RX1800-4FK04
6RA8075-6G...
174.3 A
6RX1800-4GK02
6RX1800-4FK05
Configuring
5.1 Commutating reactor rectifier assignment
SINAMICS DCM commutating reactors
24 Operating Instructions, 11/2013, A5E32621741B
SINAMICS DCM
I AC
4% reactor 50 Hz
4% reactor 60 Hz
6RA8081-6G...
332 A
6RX1800-4GK03
6RX1800-4FK07
6RA8085-6G...
498 A
6RX1800-4GK04
6RX1800-4FK10
6RA8087-6GS…
664 A
6RX1800-4GK07
6RX1800-4FK11
6RA8087-6GV...
705.5 A
6RX1800-4GK08
6RX1800-4FK12
6RA8090-6G...
913 A
6RX1800-4GK11
6RX1800-4FK13
6RA8093-4G...
1328 A
6RX1800-4GK13
6RX1800-4FK15
6RA8095-4G...
1660 A
6RX1800-4GK14
6RX1800-4FK16
6RA8096-4G...
1826 A
6RX1800-4GK15
6RX1800-4FK17
6RA8097-4G...
2324 A
6RX1800-4GK17
6RX1800-4FK18
3-ph. 690 V AC
6RA8086-6KS…
597.6 A
6RX1800-4KK00
6RX1800-4GK05
6RA8086-6KV...
630.8 A
6RX1800-4KK01
6RX1800-4GK06
6RA8090-6K...
830 A
6RX1800-4KK03
6RX1800-4GK10
6RA8093-4K...
1245 A
6RX1800-4KK04
6RX1800-4GK12
6RA8095-4K...
1660 A
6RX1800-4KK06
6RX1800-4GK14
6RA8097-4K...
2158 A
6RX1800-4KK07
6RX1800-4GK16
3-ph. 830 V AC
6RA8088-6L...
788.5 A
6RX1800-4LK00
6RX1800-4KK02
6RA8093-4L... 1245 A 6RX1800-4LK01 6RX1800-4KK04
6RA8095-4L...
1577 A
6RX1800-4LK02
6RX1800-4KK05
3-ph. 950 V AC
6RA8096-4M...
1826 A
6RX1800-4MK00
6RX1800-4LK03
1-phase commutating reactors assignment
The 1-phase commutating reactors are selected based on the field rated current of the
SINAMICS DCM.
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 25
Technical data
6
General technical specifications
Degree of protection
IP00
Safety class
Class 1 (see also note below)
Cooling
AN, self-ventilated
Inductance tolerance
±10 %
Environmental classes according to
DIN
IEC 60721-3 Parts 1 to 3
Climatic:
Storage
Transport
Operation
1K3
2K2
3K3
Mechanical:
3M3
Ambient Temperature during Operation
1-phase reactors
3-phase reactors
0
to +45° C, above with derating
0
to +40° C, above with derating
Ambient temperature
storage and transport
-
40° to +70° C
Inst
allation altitude
(at rated current)
≤ 1000 m above sea level, above with
derating
Operation at 50 Hz and 60 Hz with rated current is permissible
Note
Declaration for protection class 1
Despite protective conductor connection, no 'touchable conductiv
e parts' with regard to the
standard (e.g. EN
61800-5-1) are defined.
In this case, the protective conductor ensures that no dangerous voltages/currents can act at
the mounting surfaces.
The complete reactor must be considered as being an active part.
Technical data
SINAMICS DCM commutating reactors
26 Operating Instructions, 11/2013, A5E32621741B
Derating
Figure 6-1 Derating as a function of the ambient temperature
Figure 6-2 Derating as a function of the installation altitude
Technical data
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 27
Inductance curve
LN Rated inductance Irated Rated current of the commutating
reactor
LX
Inductance at IX
IX
Current in the commutating reactor
Figure 6-3 Typical inductance curve
Technical data
SINAMICS DCM commutating reactors
28 Operating Instructions, 11/2013, A5E32621741B
Specific technical data
Dimensions, see Section Dimension drawings (Page 33).
3-phase commutating reactors
Table 6- 1 Commutating reactors 3ph
uk=4 % for rated current and 3AC 400 V/50 Hz or 3AC 480 V/60 Hz
Order
number
6RX1800-..
AC rated
current
DC rated
current
Inductance
Copper
losses
Total
losses
SCCR
Weight
Rated
insulating
voltage
Insulating
material
class
according
to
DIN EN
60085
4DK00 13 A 15 A 2.315 mH 22.8 W 33.1 W 2.0 kA
(20 ms)
2.9 kg 600 V B
4DK01 25 A 30 A 1.158 mH 30.8 W 53.2 W 5.0 kA
(20 ms)
4.4 kg 600 V B
4DK02 51 A 60 A 0.579 mH 43.5 W 73.2 W 6.5 kA
(100 ms)
10.9 kg 600 V B
4DK03 76 A 90 A 0.386 mH 64.4 W 118.5 W 9.0 kA
(100 ms)
13.8 kg 600 V B
4DK04 106 A 125 A 0.278 mH 51.3 W 119.3 W 15 kA
(100 ms)
23.9 kg 600 V B
4DK05 174 A 210 A 0.169 mH 164.8 W 206.4 W 15 kA
(100 ms)
24.0 kg 600 V F
4DK06 232 A 280 A 0.127 mH 197.4 W 256.2 W 20 kA
(100 ms)
26.8 kg 600 V F
4DK07 332 A 400 A 0.089 mH 190.7 W 251.1 W 24 kA
(200 ms)
45.8 kg 600 V F
4DK08 374 A 450 A 0.079 mH 186.7 W 251.7 W 24 kA
(200 ms)
56.8 kg 600 V F
4DK10 498 A 600 A 0.059 mH 277.0 W 357.4 W 35 kA
(200 ms)
60.0 kg 600 V F
4DK11 706 A 850 A 0.042 mH 329.4 W 424.8 W 55 kA
(200 ms)
81.6 kg 1000 V F
4DK12 996 A 1200 A 0.030 mH 390.3 W 562.8 W 75 kA
(200 ms)
100.1 kg 1000 V F
4DK13 1328 A 1600 A 0.022 mH 339.3 W 554.5 W 75 kA
(200 ms)
138.8 kg 1000 V F
4DK14 1660 A 2000 A 0.018 mH 369.3 W 591.9 W 75 kA
(200 ms)
210.7 kg 1000 V F
4DK15 2490 A 3000 A 0.012 mH 587.3 W 1038.3 W 75 kA
(200 ms)
205.6 kg 1000 V F
Technical data
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 29
Table 6- 2 Commutating reactors 3ph
uk=4 % for rated current and 3AC 480 V/50 Hz or 3AC 575 V/60 Hz
Order
number
6RX1800-..
AC rated
current
DC rated
current
Inductance
Copper
losses
Total
losses
SCCR
Weight
Rated
insulating
voltage
Insulating
material
class
according
to
DIN EN
60085
4FK00 13 A 15 A 2.779 mH 27.4 W 39.2 W 2.0 kA
(20 ms)
2.9 kg 600 V B
4FK01 25 A 30 A 1.389 mH 34.8 W 57.8 W 5.0 kA
(20 ms)
6.0 kg 600 V B
4FK02 51 A 60 A 0.695 mH 42.3 W 77.2 W 6.5 kA
(100 ms)
11.8 kg 600 V B
4FK03 76 A 90 A 0.463 mH 56.3 W 118.0 W 9.0 kA
(100 ms)
16.3 kg 600 V B
4FK04 106 A 125 A 0.333 mH 68.8 W 152.9 W 15 kA
(100 ms)
22.3 kg 600 V B
4FK05 174 A 210 A 0.202 mH 204.6 W 255.6 W 15 kA
(100 ms)
26.0 kg 600 V F
4FK06 232 A 280 A 0.152 mH 178.3 W 231.4 W 20 kA
(100 ms)
37.8 kg 600 V F
4FK07 332 A 400 A 0.106 mH 193.7 W 261.5 W 24 kA
(100 ms)
56.1 kg 600 V F
4FK08 374 A 450 A 0.094 mH 189.1 W 279.2 W 24 kA
(100 ms)
56.8 kg 600 V F
4FK10 498 A 600 A 0.071 mH 313.8 W 396.9 W 35 kA
(200 ms)
78.1 kg 1000 V F
4FK11 664 A 800 A 0.053 mH 255.6 W 360.8 W 75 kA
(200 ms)
96.6 kg 1000 V F
4FK12 706 A 850 A 0.050 mH 293.9 W 404.1 W 75 kA
(200 ms)
96.6 kg 1000 V F
4FK13 913 A 1100 A 0.039 mH 375.6 W 558.6 W 75 kA
(200 ms)
114.5 kg 1000 V F
4FK14 996 A 1200 A 0.035 mH 332.7 W 532.8 W 75 kA
(200 ms)
127.8 kg 1000 V F
4FK15 1328 A 1600 A 0.027 mH 320.4 W 573.7 W 75 kA
(200 ms)
177.6 kg 1000 V F
4FK16 1660 A 2000 A 0.021 mH 436.5 W 819.0 W 75 kA
(200 ms)
161.0 kg 1000 V F
4FK17 1326 A 2200 A 0.019 mH 464.7 W 819.9 W 75 kA
(200 ms)
164.2 kg 1000 V F
4FK18 2324 A 2800 A 0.015 mH 671.8 W 1056.7 W 75 kA
(200 ms)
258.2 kg 1000 V F
Technical data
SINAMICS DCM commutating reactors
30 Operating Instructions, 11/2013, A5E32621741B
Table 6- 3 Commutating reactors 3ph
uk=4 % for rated current and 3AC 575 V/50 Hz or 3AC 690 V/60 Hz
Order
number
6RX1800-..
AC rated
current
DC rated
current
Inductance
Copper
losses
Total
losses
SCCR
Weight
Rated
insulating
voltage
Insulating
material
class
according
to
DIN EN
60085
4GK00 51 A 60 A 0.832 mH 56.8 W 109.7 W 6.5 kA
(100 ms)
13.6 kg 600 V B
4GK01 106 A 125 A 0.399 mH 65.6 W 156.7 W 15 kA
(100 ms)
26.4 kg 600 V B
4GK02 174 A 210 A 0.243 mH 150.0 W 200.5 W 15 kA
(100 ms)
34.5 kg 600 V F
4GK03 332 A 400 A 0.127 mH 252.1 W 327.3 W 24 kA
(200 ms)
63.1 kg 600 V F
4GK04 498 A 600 A 0.085 mH 330.3 W 427.5 W 35 kA
(200 ms)
86.0 kg 1000 V F
4GK05 598 A 720 A 0.071 mH 339.6 W 455.5 W 55 kA
(200 ms)
89.8 kg 1000 V F
4GK06 631 A 760 A 0.067 mH 322.8 W 441.1 W 55 kA
(200 ms)
95.7 kg 1000 V F
4GK07 664 A 800 A 0.064 mH 380.7 W 547.2 W 75 kA
(200 ms)
108.4 kg 1000 V F
4GK08 706 A 850 A 0.060 mH 392.7 W 564.5 W 75 kA
(200 ms)
120.6 kg 1000 V F
4GK10 830 A 1000 A 0.051 mH 308.1 W 498.3 W 75 kA
(200 ms)
134.8 kg 1000 V F
4GK11 913 A 1100 A 0.046 mH 320.7 W 515.9 W 75 kA
(200 ms)
143.9 kg 1000 V F
4GK12 1245 A 1500 A 0.034 mH 371.4 W 605.4 W 75 kA
(200 ms)
206.1 kg 1000 V F
4GK13 1328 A 1600 A 0.032 mH 503.1 W 812.4 W 75 kA
(200 ms)
160.9 kg 1000 V F
4GK14 1660 A 2000 A 0.025 mH 631.3 W 993.1 W 75 kA
(200 ms)
202.0 kg 1000 V F
4GK15 1826 A 2200 A 0.023 mH 614.7 W 1006.9 W 75 kA
(200 ms)
212.1 kg 1000 V H
4GK16 2158 A 2600 A 0.020 mH 534.6 W 1073.7 W 75 kA
(200 ms)
303.0 kg 1000 V F
4GK17 2324 A 2800 A 0.018 mH 556.2 W 1110.0 W 75 kA
(200 ms)
321.6 kg 1000 V F
Technical data
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 31
Table 6- 4 Commutating reactors 3ph
uk=4 % for rated current and 3AC 690 V/50 Hz or 3AC 830 V/60 Hz
Order
number
6RX1800-..
AC rated
current
DC rated
current
Inductance
Copper
losses
Total
losses
SCCR
Weight
Rated
insulating
voltage
Insulating
material
class
according
to
DIN EN
60085
4KK00 598 A 720 A 0.085 mH 388.2 W 562.1 W 55 kA
(200 ms)
108.9 kg 1000 V F
4KK01 631 A 760 A 0.080 mH 402.0 W 586.4 W 75 kA
(200 ms)
113.3 kg 1000 V F
4KK02 789 A 950 A 0.064 mH 362.7 W 564.6 W 75 kA
(200 ms)
141.9 kg 1000 V F
4KK03 830 A 1000 A 0.061 mH 350.7 W 561.4 W 75 kA
(200 ms)
153.4 kg 1000 V F
4KK04 1245 A 1500 A 0.041 mH 505.2 W 845.7 W 75 kA
(200 ms)
169.7 kg 1000 V F
4KK05 1577 A 1900 A 0.032 mH 716.8 W 1093.8 W 75 kA
(200 ms)
226.1 kg 1000 V F
4KK06 1660 A 2000 A 0.031 mH 596.0 W 1011.8 W 75 kA
(200 ms)
257.2 kg 1000 V F
4KK07 2158 A 2600 A 0.024 mH 484.8 W 1185.6 W 75 kA
(200 ms)
360.2 kg 1000 V F
Table 6- 5 Commutating reactors 3ph
uk=4 % for rated current and 3AC 830 V/50 Hz or 3AC 950 V/60 Hz
Order
number
6RX1800-..
AC rated
current
DC rated
current
Inductance
Copper
losses
Total
losses
SCCR
Weight
Rated
insulating
voltage
Insulating
material
class
according
to
DIN EN
60085
4LK00 789 A 950 A 0.077 mH 312.0 W 532.1 W 75 kA
(200 ms)
205.2 kg 1000 V F
4LK01 1245 A 1500 A 0.049 mH 692.4 W 1061.9 W 75 kA
(200 ms)
222.4 kg 1000 V F
4LK02 1577 A 1900 A 0.039 mH 479.4 W 1059.6 W 75 kA
(200 ms)
308.5 kg 1000 V F
4LK03 1826 A 2200 A 0.033 mH 585.6 W 1269.0 W 75 kA
(200 ms)
372.5 kg 1000 V F
Technical data
SINAMICS DCM commutating reactors
32 Operating Instructions, 11/2013, A5E32621741B
Table 6- 6 Commutating reactor 3ph
uk=4 % for rated current and 3AC 950 V/50 Hz, operation at 60 Hz and rated current permissible
Order
number
6RX1800-..
AC rated
current
DC rated
current
Inductance
Copper
losses
Total
losses
SCCR
Weight
Rated
insulating
voltage
Insulating
material
class
according
to
DIN EN
60085
4MK00 1826 A 2200 A 0.038 mH 534.9 W 1303.5 W 75 kA
(200 ms)
399.7 kg 1000 V F
1-phase commutating reactors
Table 6- 7 Commutating reactors 1ph
uk=4 % for rated current and 1AC 400 V/50 Hz or 1AC 480 V/60 Hz
Order
number
6RX1800-..
AC rated
current
DC rated
current
Inductance
Copper
losses
Total
losses
SCCR
Weight
Rated
insulating
voltage
Insulating
material
class
according
to
DIN EN
60085
4DE00 3 A 3 A 16.98 mH 3 W 5 W 0.8 kA
(20 ms)
0.7 kg 600 V B
4DE01 5 A 5 A 10.19 mH 5 W 7 W 0.8 kA
(20 ms)
1.5 kg 600 V B
4DE02 10 A 10 A 5.090 mH 7 W 12 W 2 kA
(20 ms)
2.0 kg 600 V B
4DE03 15 A 15 A 3.400 mH 8 W 17 W 2 kA
(20 ms)
2.3 kg 600 V B
4DE04 25 A 25 A 2.040 mH 8 W 29 W 6 kA
(20 ms)
3.0 kg 600 V B
4DE05 30 A 30 A 1.700 mH 10 W 30 W 6 kA
(20 ms)
3.8 kg 600 V B
4DE06 40 A 40 A 1.270 mH 9 W 49 W 10 kA
(20 ms)
5.2 kg 600 V B
4DE07 85 A 85 A 0.600 mH 13 W 67 W 15 kA
(20 ms)
9.6 kg 600 V B
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 33
Dimension drawings
7
Dimensions in mm
Type: 6RX1800-4DK00, 6RX1800-4FK00
Dimension drawings
SINAMICS DCM commutating reactors
34 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4DK01
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 35
Type: 6RX1800-4FK01
Dimension drawings
SINAMICS DCM commutating reactors
36 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4DK02, 6RX1800-4FK02
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 37
Type: 6RX1800-4GK00, 6RX1800-4DK03, 6RX1800-4FK03
Dimension drawings
SINAMICS DCM commutating reactors
38 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4DK04
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 39
Type: 6RX1800-4FK04
Dimension drawings
SINAMICS DCM commutating reactors
40 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4GK01
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 41
Type: 6RX1800-4DK05, 6RX1800-4FK05, 6RX1800-4DK06
Dimension drawings
SINAMICS DCM commutating reactors
42 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4GK02, 6RX1800-4FK06
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 43
Type: 6RX1800-4DK07
Dimension drawings
SINAMICS DCM commutating reactors
44 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4DK08, 6RX1800-4FK07, 6RX1800-4FK08
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 45
Type: 6RX1800-4GK03, 6RX1800-4DK10
Dimension drawings
SINAMICS DCM commutating reactors
46 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4FK10, 6RX1800-4GK04
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 47
Type: 6RX1800-4DK11
Dimension drawings
SINAMICS DCM commutating reactors
48 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4GK05, 6RX1800-4GK06, 6RX1800-4FK11, 6RX1800-4FK12
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 49
Type: 6RX1800-4KK00, 6RX1800-4KK01, 6RX1800-4GK07, 6RX1800-4GK08
Dimension drawings
SINAMICS DCM commutating reactors
50 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4FK13, 6RX1800-4DK12
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 51
Type: 6RX1800-4KK02, 6RX1800-4GK10, 6RX1800-4KK03,
6RX1800-4GK11, 6RX1800-4FK14
Dimension drawings
SINAMICS DCM commutating reactors
52 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4LK00
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 53
Type: 6RX1800-4DK13
Dimension drawings
SINAMICS DCM commutating reactors
54 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4DK14, 6RX1800-4GK12, 6RX1800-4FK15
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 55
Type: 6RX1800-4KK04, 6RX1800-4GK13, 6RX1800-4FK16, 6RX1800-4FK17
Dimension drawings
SINAMICS DCM commutating reactors
56 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4LK01, 6RX1800-4KK05, 6RX1800-4GK14,
6RX1800-4KK06, 6RX1800-4GK15, 6RX1800-4FK18, 6RX1800-4DK15
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 57
Type: 6RX1800-4LK02, 6RX1800-4GK16, 6RX1800-4GK17
Dimension drawings
SINAMICS DCM commutating reactors
58 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4LK03, 6RX1800-4MK00, 6RX1800-4KK07
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 59
Type: 6RX1800-4DE00
Dimension drawings
SINAMICS DCM commutating reactors
60 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4DE01
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 61
Type: 6RX1800-4DE02
Dimension drawings
SINAMICS DCM commutating reactors
62 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4DE03
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 63
Type: 6RX1800-4DE04
Dimension drawings
SINAMICS DCM commutating reactors
64 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4DE05
Dimension drawings
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 65
Type: 6RX1800-4DE06
Dimension drawings
SINAMICS DCM commutating reactors
66 Operating Instructions, 11/2013, A5E32621741B
Type: 6RX1800-4DE07
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 67
Appendix
A
A.1
Customer Service
Service
You can find information on our services and regional contact persons in the Internet -
(http://support.automation.siemens.com/WW/view/en/16604318)
Technical Support
Our technical support can provide you with technical assistance for products, systems, and
solutions:
German (www.siemens.de/automation/support-request)
English (www.siemens.com/automation/support-request)
Central hotlines for SINAMICS DCM technical support
European and African time
zone
Phone: +49 (0)911 895 7222
Fax: +49 (0)911 895 7223
email (mailto:support.automation@siemens.com)
8:00 to 17:00 CET
America time zone
24-hour hotline: +1 800 333 7421
Phone: +1 423 262 2960
Fax: +1 423 262 2200
email
(mailto:support.america.automation@siemens.com)
8:00 to 17:00
Eastern Standard Time
Asia/Australia time zone Phone: +86 1064 757575
Fax: +86 1064 747474
email (mailto:support.asia.automation@siemens.com)
7:30 to 17:30
Beijing local time
Appendix
A.2 Environment
SINAMICS DCM commutating reactors
68 Operating Instructions, 11/2013, A5E32621741B
A.2
Environment
Siemens feels a responsibility to play a role in protecting our environment and saving our
valuable natural resources. This is true for both our production and our products.
Even during development, we consider any possible environmental impact of future
products/systems. Our aim is to prevent harmful environmental effects or at least to reduce
them to an absolute minimum above and beyond present regulations and legislation.
Environmental aspects during development
The use of hazardous substances (e.g. arsenic, asbestos, beryllium, cadmium, CFCS,
halogen) has been avoided from the development stage onward.
Particular emphasis has been placed on ensuring that the range of metal and plastic parts is
kept to a minimum. Pollutant-free materials have been used for all significant parts. No flame
retardants containing halogen or insulation materials containing silicone have been used.
Environmental compatibility was a key criterion in selecting supplier parts.
Plastic parts:
Zytel 73G30L (E41938)
Rynite FR530L (E41938)
Revitex VPG (E121222)
UTR 1494 (E23525)
Voltaflex 2589
Impregnating resin:
Voltatex 4001 (E101752)
Shipping
For the selection and form of our packaging, we value environmental compatibility, reuse
and, in particular, waste avoidance. The packing material itself is recyclable, and consists
mainly of cardboard. Surface coatings have been omitted as far as possible.
Appendix
A.3 Standards, certifications
SINAMICS DCM commutating reactors
Operating Instructions, 11/2013, A5E32621741B 69
A.3
Standards, certifications
EN 61558
-1
Safety of transformers, reactors, power supplies and the associated
combinations
Part 1: General requirements
EN
61558-2-20
Safety of transformers, reactors, power supplies and the associated
combination
s
Part 2-20: Special requirements and tests for small reactors
EP standard
No. 1
Requirements placed on the environmental compatible product and
system layout
EN
60721-3-1
EN
60721-3-2
EN 60721-3-3
Classification of environmental conditions
EN60939-2
Passive filters for the suppression of electromagnetic disturbances
ROHS
Restriction of Hazardous Substances
REACH
Registration, Evaluation, Authorisation and Restriction of Chemicals
CSA 22.2 No. 66
Low Voltage Transformers - Part 1: General Requirements
UL5085-1
Low Voltage Transformers - Part 1: General Requirements
Appendix
A.3 Standards, certifications
SINAMICS DCM commutating reactors
70 Operating Instructions, 11/2013, A5E32621741B
Siemens AG
Industry Sector
P.O. Box 48 48
90026 NUREMBERG
GERMANY
Subject to change
A5E32621741B
© Siemens AG 2013
DC Converters
SINAMICS DCM
www.siemens.com/automation